Ramp Differential Expansion Monitor Maintenance
84414-01
8
Alarm Setpoint Adjust
1. Open front panel.
2. Set switch the Setpoint Adjust switch
(SA) to the left (ON).
3. Select Short rotor setpoints by setting
the Long/Short (US) switch to the right.
The left bargraph will start flashing the
differential expansion signal.
4. To adjust Alert or Danger setpoints,
press a n d h o l d ALERT o r DANGER
switch on the front panel.
5. Use the ( r ) o r (4.) switches on the
System Monitor to adjust the setpoint
level up or down.
6. Repeat for Long setpoints by setting
the Long/Short (US) switch to the left.
7. Reset SA to the right (OFF).
8. Close front panel.