t(off )
Delay on release
t
off
Starts when the condition that triggers the message (for pre-
warning or main alarm) no longer exists. The RCMS150…
only stops signalling if the condition that triggers the mes-
sage no longer exists after the delay on release has elapsed.
Setting range: 0…10 minutes.
t(on)
Response delay
t
on
Starts when a condition that triggers the message (for pre-
warning and main alarm) exists. Signalling is only done by
the RCMS150… if the condition that triggers the message
still exists after the response delay has elapsed.
Setting range: 0…10 minutes.
t(start-up)
Start-up delay
t
start-up
Time delay after the RCMS150 has been switched on. No
alarm message is generated during this time period. This
time delay is required if the RCMS150… and the system to
be monitored are switched on simultaneously. Currents
caused by switching operations are ignored.
Setting range: 500 ms…10 minutes.
Terms
Explanation