Overview Modbus registers (RCMS150-01 only)
35
RCMS150_D00259_01_M_XXEN/08.2021
32178
Reserved
32180
RW
K4
Response value hys-
teresis
Float32
%
10…25 %
0.1 %
15 %
32182
RW
t
off
Float32
s
0 s…10 min
10 ms
1 s
32184
RW
t
start-up
Float32
s
0.5 s…10 min
10 ms
0.5 s
32186
RW
Fault memory
UINT16
—
0 = off; 1 = on
—
0 (off )
32187
Reserved
32188
RW
I
Δn2 RMS
Float32
A
3…300 mA
0.1 mA 30 mA
32190
RW
t
on
main alarm RMS
Float32
s
0 s…10 min
10 ms
0 s
32192
RW
I
Δn1 RMS
Float32
%
50…100 %
0.1 %
50 %
32194
RW
t
on
prewarning RMS Float32
s
0 s…10 min
10 ms
1 s
32196
RW
I
Δn2
DC
Float32
A
3…300 mA
0.1 mA
6 mA
32198
RW
t
on
main alarm DC
Float32
s
0 s…10 min
10 ms
0 s
32200
RW
I
Δn1 DC
Float32
%
50…100 %
0.1 %
50 %
32202
RW
t
on
prewarning DC
Float32
s
0 s…10 min
10 ms
1 s
32204
Reserved
Register
Property
Description
Format
Unit
Setting range
Step size
Factory
setting