Mounting, connection and commissioning
18
RCMS150_D00259_01_M_XXEN/08.2021
4.4 Commissioning
1. Mount the RCMS150…
2. Set the bus address
3. Bus installation
Please note that both the beginning and end of the bus require a 120-Ω terminat-
ing resistor.
When assigning the bus addresses make sure that each address is only
assigned once on the bus!
Address setting RCMS150 (BMS bus)
Factory setting bus address
2
Setting range BMS bus
2…90
Adjustment on the device
Move the detent potentiometers to the corresponding
position using a screwdriver.
Address setting RCMS150-01 (Modbus RTU)
Factory setting bus address
(Detent potentiometers to
00)
Last two digits of the serial 100
Setting range Modbus RTU
1…247
Addresses 1…99:
Adjustment on the device
Move the detent potentiometers to the corresponding
position using a screwdriver.
Addresses 1…247:
Adjustment via the bus
Set the detent potentiometers to 00 using a screwdriver.
Now the internally stored address (factory setting) is active.
It can be changed via the interface.