![Bender LINETRAXX RCMS150 Manual Download Page 25](http://html.mh-extra.com/html/bender/linetraxx-rcms150/linetraxx-rcms150_manual_2731702025.webp)
Overview Modbus registers (RCMS150-01 only)
25
RCMS150_D00259_01_M_XXEN/08.2021
6.1.3
Overview of the register ranges
6.2 Device information
Range
Start address
End address
Info
0
999
Measured values
1000
31999
Interface parameters
32000
32099
Parameters
32100
57999
Control commands
59000
59999
Register
Property
Description
Format
Comment/Factory settings*
00000
RO
Modbus
test register
UINT32
0x12345678*
Is used to configure the
interface (endianess, byte
order, etc.).
00002
RO
Device name
String UTF8 RCMS150-01\0*
00018
RO
Article number
String UTF8 B94053026\0*
00034
RO
Serial number
String UTF8 —
00050
RO
Manufacturer name
String UTF8 Bender\0*
00066
RO
Manufacturer Internet
address
String UTF8 www.bender.de\0*
00082
RO
Device version
UINT16
Version number multi-
plied by 100.
Example: 123 = V1.23
00083
RO
Device patch version
UINT16
—
00084
RO
IU application D number
UINT16
657*
00085
RO
IU application Version
UINT16
—
00086
RO
IU application Build number
UINT16
—
00087
RO
IU application Modbus mod-
ule version
UINT16
—
00088
RO
IU Bootloader D number
UINT16
711*
00089
RO
IU Bootloader Version
UINT16
—
00090
RO
IU Bootloader
Build number
INT16
—