![Bender LINETRAXX RCMS150 Manual Download Page 33](http://html.mh-extra.com/html/bender/linetraxx-rcms150/linetraxx-rcms150_manual_2731702033.webp)
Overview Modbus registers (RCMS150-01 only)
33
RCMS150_D00259_01_M_XXEN/08.2021
6.5 Parameters
Register
Property
Description
Format
Unit
Setting range
Step size
Factory
setting
32100
Reserved
32102
RW
K1
Response value
Hysteresis
Float32
%
10…25 %
0.1 %
15 %
32104
RW
t
off
Float32
s
0 s …10 min
10 ms
1 s
32106
RW
t
start-up
Float32
s
0.5 s…10 min
10 ms
0.5 s
32108
RW
Fault memory
UINT16
—
0 = off; 1 = on
—
0 (off )
32109
Reserved
32110
RW
I
Δn2 RMS
Float32
A
3…300 mA
0.1 mA 30 mA
32112
RW
t
on
main alarm RMS
Float32
s
0 s…10 min
10 ms
0 s
32114
RW
I
Δn1 RMS
Float32
%
50…100 %
0.1 %
50 %
32116
RW
t
on
prewarning RMS Float32
s
0 s…10 min
10 ms
1 s
32118
RW
I
Δn2
DC
Float32
A
3…300 mA
0.1 mA
6 mA
32120
RW
t
on
main alarm DC
Float32
s
0 s…10 min
10 ms
0 s
32122
RW
I
Δn1 DC
Float32
%
50…100 %
0.1 %
50 %
32124
RW
t
on
prewarning DC
Float32
s
0 s…10 min
10 ms
1 s
32126
Reserved