![Bender LINETRAXX RCMS150 Manual Download Page 36](http://html.mh-extra.com/html/bender/linetraxx-rcms150/linetraxx-rcms150_manual_2731702036.webp)
Overview Modbus registers (RCMS150-01 only)
36
RCMS150_D00259_01_M_XXEN/08.2021
32206
RW
K5
Response value hys-
teresis
Float32
%
10…25 %
0.1 %
15 %
32208
RW
t
off
Float32
s
0 s…10 min
10 ms
1 s
32210
RW
t
start-up
Float32
s
0.5 s…10 min
10 ms
0.5 s
32212
RW
Fault memory
UINT16
—
0 = off; 1 = on
—
0 (off )
32213
Reserved
32214
RW
I
Δn2 RMS
Float32
A
3…300 mA
0.1 mA 30 mA
32216
RW
t
on
main alarm RMS
Float32
s
0 s…10 min
10 ms
0 s
32218
RW
I
Δn1 RMS
Float32
%
50…100 %
0.1 %
50 %
32220
RW
t
on
prewarning RMS Float32
s
0 s…10 min
10 ms
1 s
32222
RW
I
Δn2
DC
Float32
A
3…300 mA
0.1 mA
6 mA
32224
RW
t
on
main alarm DC
Float32
s
0 s…10 min
10 ms
0 s
32226
RW
I
Δn1 DC
Float32
%
50…100 %
0.1 %
50 %
32228
RW
t
on
prewarning DC
Float32
s
0 s…10 min
10 ms
1 s
32230
Reserved
32232
RW
K6
Response value hys-
teresis
Float32
%
10…25 %
0.1 %
15 %
32234
RW
t
off
Float32
s
0 s…10 min
10 ms
1 s
32236
RW
t
start-up
Float32
s
0.5 s…10 min
10 ms
0.5 s
32238
RW
Fault memory
UINT16
—
0 = off; 1 = on
—
0 (off )
32239
Reserved
32240
RW
I
Δn2 RMS
Float32
A
3…300 mA
0.1 mA 30 mA
32242
RW
t
on
main alarm RMS
Float32
s
0 s…10 min
10 ms
0 s
32244
RW
I
Δn1 RMS
Float32
%
50…100 %
0.1 %
50 %
32246
RW
t
on
prewarning RMS Float32
s
0 s…10 min
10 ms
1 s
32248
RW
I
Δn2
DC
Float32
A
3…300 mA
0.1 mA
6 mA
32250
RW
t
on
main alarm DC
Float32
s
0 s…10 min
10 ms
0 s
32252
RW
I
Δn1 DC
Float32
%
50…100 %
0.1 %
50 %
32254
RW
t
on
prewarning DC
Float32
s
0 s…10 min
10 ms
1 s
Register
Property
Description
Format
Unit
Setting range
Step size
Factory
setting
Summary of Contents for LINETRAXX RCMS150
Page 48: ...Technical data 48 RCMS150_D00259_01_M_XXEN 08 2021 ...