isoNAV685-D_D00215_02_M_XXEN/04.2017
46
Factory settings
15. Factory settings
Parameter
Value
Response values/alarms
Response value R
an1
(ALARM 1)
5 kΩ
Response value R
an2
+ DC offset voltage
(ALARM 2)
150 V
Fault memory
off
Coupling monitoring
on
System
System type
3AC
Profile
Power circuits
Coupling devices
Coupling
none
Time response
Start-up delay T
start-up
0 s
Digital inputs
Digital input 1
Mode (Operating mode)
Active high
Function
Deactivate device
Digital input 3
Mode (Operating mode)
Active high
Function
Deactivate device
Digital outputs
Digital output 1
Function 1
Insulation fault + DC offset voltage
Switching elements
Relay 1
Operating mode
N/C operation
Function 1
Ins. alarm 1
Relay 2
Operating mode
N/C operation
Function 1
Ins. alarm 2 + DC offset voltage
Interfaces
DHCP
off
IP address
192.168.0.5
Net mask
255.255.255.0
BCOM address
system-1-0
Parameter