Display
Display
isoNAV685-D_D00215_02_M_XXEN/04.2017
23
8.2 Fault display (active)
An active fault is displayed by
. The upper part of the display will become orange and
displays the fault message.
Depending on the type of fault, the LEDs ALARM 1, ALARM 2 or SERVICE are activated.
In the example below, the insulation resistance is 3 kΩ. Because the measured insulation
value is below the set response insulation resistance value of
R
an
=5 kΩ and the DC offset
voltage response value of 150 V has been exceeded, Alarm 1 and Alarm 2 have been trig-
gered. In addition, information concerning the DC-shift is also displayed.
If several fault messages occur, you can navigate through the faults using the and
buttons.
ALARM 1 lights
Insulation fault
ALARM 1 + 2 lights
Insulation fault + DC shift error
ALARM 1 + 2 blinks
Connection fault
SERVICE lights up
Device fault
3 kΩ
Insulation fault
1/4
3 kΩ
8.3 Fault display (inactive)
An inactive fault is displayed by
. If several faults have occurred, the number of faults
will also be indicated.
This message means that there has been a fault in the past but the device is no longer in
fault condition.
2 3 0
kΩ
IT
System
3x
1/4
2 3 0 kΩ