Modbus settings
isoNAV685-D_D00215_02_M_XXEN/04.2017
64
//AnalogOutFunctions
0x30C1u
12481
Analogue Output
Function
2
Uint16
R/W
1 = Insulation value
2 = DC shift
1…2
0x30C2u
12482
Analogue Output
Mode
2
Uint16
R/W
1 = 0…20 mA
2 = 4…20 mA
3 = 0… 400 µA
4 = 0…10 V
5 = 2…10 V
1…5
0x30C3u
12483
Analogue Output
Midscale
2
Uint16
R/W
1 = Linear
2 = 28 kΩ
3 = 120 kΩ
1…3
0x30C4u
12484
Analogue Output
Test
2
Uint16
R/W
1 = Test on
2 = Test off
1…2
//BuzzerFunctions
0x30C5u
12485
Summer Function 1
2
Uint16
R/W
see 0x30B7u
1…11
0x30C6u
12486
Summer Function 2
2
Uint16
R/W
see 0x30B7u
1…11
0x30C7u
12487
Summer Function 3
2
Uint16
R/W
see 0x30B7u
1…11
0x30C8u
12488
Summer Test
2
Uint16
R/W
1 = Test on
2 = Test off
1…2
//RelayOutFunctions
0x30C9u
12489
Relay 1
Test
2
Uint16
R/W
1 = Test on
2 = Test off
1…2
0x30CAu
12490
Relay 1
Mode
2
Uint16
R/W
1 = N/O
2 = N/C
1…2
0x30CBu
12491
Relay 1
Function 1
2
Uint16
R/W
see 0x30B7u
1…11
0x30CCu
12492
Relay 1
Function 2
2
Uint16
R/W
see 0x30B7u
1…11
0x30CDu
12493
Relay 1
Function 3
2
Uint16
R/W
see 0x30B7u
1…11
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range
Unit