![Bender ISOMETER iso1685FR Manual Download Page 40](http://html.mh-extra.com/html/bender/isometer-iso1685fr/isometer-iso1685fr_manual_2731645040.webp)
Parameterization via the BMS bus
40
iso1685FR(M)_D00002_02_M_XXEN/06.2017
7.2.3 Error handling
If the displayed values do not correspond to the conditions of the installation after parameterization, R
e-Anlage
and C
e-Anlage
must be set again. Refer to the iso1685FR-Set quickstart for operating instructions.
If the parameters do not correspond with the conditions of the installation, an ohmic insulation value deviating
from R
e_Anlage
is output for R
e
instead of the real value after initial commissioning.If the value of R
e
cannot be
determined, a default value of 1 MΩ is output instead.
The following errors can lead to these deviating outputs:
•
Incorrect parameterization of R
e_Anlage
:
Consequences: The value to be parameterized for C
e_Anlage
(= Ce to set) cannot be correctly determi-
ned. Error cases: a.) Ohmic insulation resistance of the installation is higher than the parameterized
value:
Output R
e
= 1 MΩ
Error handling: R
e_Anlage
and C
e_Anlage
must be parameterized again
b.) Ohmic insulation resistance of the installation is LOWER than the parameterized value: Output
R
e
= R
e
= 1 MΩ:
Error handling: R
e_Anlage
and C
e_Anlage
must be parameterized again
•
Incorrect parameterization of C
e_Anlage
:
Consequences: The resulting ohmic insulation resistance value does not correspond to the expected
value of the installation.
Error cases:
a.) System leakage capacitance of the installation is HIGHER than the parameterized value:
Output R
e
≠ R
e_Anlage
Error handling: C
e_Anlage
must be parameterized again
b.)System leakage capacitance of the installation is LOWER than the parameterized value:
Output R
e
= 1 MΩ
Error handling: C
e_Anlage
must be parameterized again
By using the iso1685FR-Set program you confirm the following conditions:
Bender provides this software free of charge and without any warranty. By using this software
you agree that you are using the software at your own risk. Bender does not assume any re-
sponsibility for possible software errors or defects and does not guarantee that the software
works error-free and reliably. Furthermore, Bender does not accept liability for direct or indi-
rect damage that may arise from the use of the software.
Summary of Contents for ISOMETER iso1685FR
Page 6: ...6 ...
Page 10: ...Important information 10 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 14: ...Safety instructions 14 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 42: ...Diagram for the calculation of Ze 42 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 44: ...Information about the measuring method 44 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 50: ...INDEX 50 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 51: ...INDEX 51 iso1685FR M _D00002_02_M_XXEN 06 2017 ...