37
iso1685FR(M)_D00002_02_M_XXEN/06.2017
7. Parameterization via the BMS bus
7.1 Parameter
7.1.1 Tabel overview
7.1.2 Parameter description
•
Channel 1 (
Z
an
/kΩ): Response value for insulation measurment (active method)
This parameter defines the response threshold for the active measurement procedure. If the insulation
value
Z
e
measured by the ISOMETER® exceeds the response value
Z
an
, then the ISOMETER® triggers an
alarm.
Depending on the system leakage capacitance C
e-Anlage
and the system insulation resistance R
e-system
,
the response value
Z
an
may not exceed a certain value so that the ISOMETER® enters the normal opera-
ting condition taking into account the hysteresis (no alarm signal). The following diagram shows how
high the response value
Z
an
can be set for different insulation conditions of the installation.
Channel
BMS
comman
d
Description
Setting range
1
Ze/kO
Response value for insulation measurment
(active method)
10…1000 (Default: 25, Step size: 1)
2
Ce-instal-
lation
/nF
Ce value [nF] (Fixed),
(System leakage capacitance)
1…200
(Default: 1, Step size: 1)
3
Re-instal-
lation
/kO
R
e
value [kΩ] (Fixed)
System insulation fault
(Good condition)
10…500 (Default: 180, Step size: 1)
4
MPT
|Ze| measured data buffer size
1…10 (Default: 4, Step size: 1)
8
EWL
Response value for insulation measurement
(passive method, threshold
U
an
[V])
0…3000 (Default: 125, Step size: 1
0 = disabled
9
SFL
Response value for interference detection
over area [%]
0…50
(Default: 15, Step size: 1
0 = disabled
10
ANZ
Monitoring of system coupling L,N
1: on (Monitoring enabled)
0: off (Monitoring disabled)
(Default: 1
11
AER
Monitoring
E/KE coupling.
1: on (Monitoring enabled)
0: off (Monitoring disabled)
(Default: 1
12
SZL
Number of interferences until a device error
[-]
0…10 (Default: 6, Step size: 1
0 = disabled
Summary of Contents for ISOMETER iso1685FR
Page 6: ...6 ...
Page 10: ...Important information 10 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 14: ...Safety instructions 14 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 42: ...Diagram for the calculation of Ze 42 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 44: ...Information about the measuring method 44 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 50: ...INDEX 50 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Page 51: ...INDEX 51 iso1685FR M _D00002_02_M_XXEN 06 2017 ...