10. Harmonics
Overview of the measured harmonics as bar graphs. Use the
and
buttons to
switch between the individual displays.
There are two possibilities to calculate the individual harmonic distortion (RMS and dis-
tortion). This setting can be made directly on the device:
Settings > Calculation
Distortion
% U
k
/ U
FUND
"Fundamental"
THD calculation of an individual harmonic
(related to the fundamental
U
1
or
I
1
)
RMS
% of RMS
"Root Mean Square", r.m.s. value:
Harmonic distortion calculation of an individual
harmonic (THF, related to the
total value
U
tot
or
I
tot
)
U
k
U
k
Σ
∞
k = 1
THF
U(k)
=
2
x 100 %
I
k
I
k
Σ
∞
k = 1
THF
I(k)
=
2
x 100 %
THD U(k) =
U
k
U
1
x 100 %
THD I(k) =
I
k
I
1
x 100 %
Summary of Contents for B93100735
Page 18: ...Device description 18 PEM735_D00084_02_M_XXEN 06 2020...
Page 34: ...Commissioning and operation 34 PEM735_D00084_02_M_XXEN 06 2020...
Page 66: ...Voltage 66 PEM735_D00084_02_M_XXEN 06 2020...
Page 68: ...Current 68 PEM735_D00084_02_M_XXEN 06 2020...
Page 72: ...Waveform 72 PEM735_D00084_02_M_XXEN 06 2020...
Page 76: ...Harmonics 76 PEM735_D00084_02_M_XXEN 06 2020...
Page 80: ...Metering 80 PEM735_D00084_02_M_XXEN 06 2020...
Page 84: ...System 84 PEM735_D00084_02_M_XXEN 06 2020...
Page 91: ...Settings 91 PEM735_D00084_02_M_XXEN 06 2020 Fig 15 6 Settings display Ethernet change settings...
Page 98: ...Settings 98 PEM735_D00084_02_M_XXEN 06 2020...
Page 112: ...Glossary and terms 112 PEM735_D00084_02_M_XXEN 06 2020...
Page 115: ......