![Bender B93100735 Manual Download Page 109](http://html1.mh-extra.com/html/bender/b93100735/b93100735_manual_2731591109.webp)
Glossary and terms
109
PEM735_D00084_02_M_XXEN/06.2020
Voltage swell
(polyphase sys-
tem)
Starts when the
U
rms
voltage of at least one
channel is above the swell threshold; ends when
the
U
rms
voltage on all measured channels is
equal to or below the swell threshold minus the
hysteresis voltage; Typically, the swell threshold
is > 110 % of
U
din
; Typically, the hysteresis is
equal to 2 % of
U
din
Voltage inter-
ruption
(single-phase
system)
Starts when the
U
rms
voltage falls below the volt-
age interruption threshold; ends when the
U
rms
voltage is equal to or greater than the voltage
interruption threshold plus the hysteresis
Typically, the swell threshold for voltage inter-
ruptions is 5 % or 10 % of
U
din
; Typically, the hys-
teresis is equal to 2 % of
U
din
Voltage inter-
ruption (poly-
phase system)
Starts when
U
rms
on all measured channels falls
below the voltage interruption swell threshold;
ends when
U
rms
on any measured channel is
equal to or greater than the interruption thresh-
old plus the hysteresis; Typically, the swell
threshold for voltage interruptions is 5 % or 10 %
of
U
din
; Typically, the hysteresis is equal to 2 % of
U
din
Standard data
recorder
DR 1…16
Trigger: timer or setpoint
Recording mode "Stop when full" or "FIFO"
Recording interval 1…3,456,000 seconds
(40 days)
Number of data points: max. 65535
for each DR 0…16 measured quantities, can be
selected from 1741 measured quantities
Timer for trigger mode: Recording delay
0…43200 s (12 h)
TEHD
Total Even Harmonic
Distortion
Total even harmonic distortion
THD
Total Harmonic
Distortion
Total harmonic distortion
Abbreviation/
Term
Long form
Description
Summary of Contents for B93100735
Page 18: ...Device description 18 PEM735_D00084_02_M_XXEN 06 2020...
Page 34: ...Commissioning and operation 34 PEM735_D00084_02_M_XXEN 06 2020...
Page 66: ...Voltage 66 PEM735_D00084_02_M_XXEN 06 2020...
Page 68: ...Current 68 PEM735_D00084_02_M_XXEN 06 2020...
Page 72: ...Waveform 72 PEM735_D00084_02_M_XXEN 06 2020...
Page 76: ...Harmonics 76 PEM735_D00084_02_M_XXEN 06 2020...
Page 80: ...Metering 80 PEM735_D00084_02_M_XXEN 06 2020...
Page 84: ...System 84 PEM735_D00084_02_M_XXEN 06 2020...
Page 91: ...Settings 91 PEM735_D00084_02_M_XXEN 06 2020 Fig 15 6 Settings display Ethernet change settings...
Page 98: ...Settings 98 PEM735_D00084_02_M_XXEN 06 2020...
Page 112: ...Glossary and terms 112 PEM735_D00084_02_M_XXEN 06 2020...
Page 115: ......