Power Quality
60
PEM735_D00084_02_M_XXEN/06.2020
Fig. 6.20: Voltage sags (detailed view on page 1 of 3)
For voltage sag classification, the percentages of the voltage levels u are summarised as
follows:
90 ≥ u ≥ 80
80 > u ≥ 70
70 > u ≥ 40
40 > u ≥ 5
5 > u
The display shows:
Note: If the "Sliding Reference Voltage U
sr
" detection method is used, the calculation should
be made using a first order and a constant set to one minute.
U
sr(n)
= 0.9967 x
U
sr(n-1)
+ 0.0033 x
U
(10/12)rms
Display text
Description
Residual Voltage
Residual voltage level
U
res
t
Duration of the voltage sag (ms)
90>u>=80
Classification of the voltage sag (% of the residual voltage)
10<t<=200
Classification of the voltage sag (duration
t
in ms)
Summary of Contents for B93100735
Page 18: ...Device description 18 PEM735_D00084_02_M_XXEN 06 2020...
Page 34: ...Commissioning and operation 34 PEM735_D00084_02_M_XXEN 06 2020...
Page 66: ...Voltage 66 PEM735_D00084_02_M_XXEN 06 2020...
Page 68: ...Current 68 PEM735_D00084_02_M_XXEN 06 2020...
Page 72: ...Waveform 72 PEM735_D00084_02_M_XXEN 06 2020...
Page 76: ...Harmonics 76 PEM735_D00084_02_M_XXEN 06 2020...
Page 80: ...Metering 80 PEM735_D00084_02_M_XXEN 06 2020...
Page 84: ...System 84 PEM735_D00084_02_M_XXEN 06 2020...
Page 91: ...Settings 91 PEM735_D00084_02_M_XXEN 06 2020 Fig 15 6 Settings display Ethernet change settings...
Page 98: ...Settings 98 PEM735_D00084_02_M_XXEN 06 2020...
Page 112: ...Glossary and terms 112 PEM735_D00084_02_M_XXEN 06 2020...
Page 115: ......