Power Quality
64
PEM735_D00084_02_M_XXEN/06.2020
Note 2
: The energy content of a transient overvoltage varies considerably according to the
origin. An induced overvoltage due to lightning generally has a higher amplitude but lower
energy content than an overvoltage caused by switching, because of the generally longer
duration of such switching overvoltages.
Note 3:
For withstanding transient overvoltages in the vast majority of cases, LV
installations and end user appliances are designed according to EN 60664-1. Where
necessary (see IEC 60364-4-44), surge protection devices should be selected according to IEC
60364-5-53, to take account of the actual situations. This is assumed to cover also induced
overvoltages due to both lightning and switching.