8.6 Overload/short circuit of the Type
B port aux. power supply
8 Diagnostics processing
8.6 Overload/short circuit of the Type B port
aux. power supply
8.6.1 For LioN-P 30 devices
In case of an overload or a short circuit between pin 2 and pin 5 on these
ports (X5 - X8), the following group diagnostic message (non channelspecific)
is generated:
Channel number of diagnosis
0x8000 (diagnosis not channel-specific)
Channel related diagnosis
code
0x0108
Channel related diagnosis
code message
Short circuit or overload of auxiliary power supply at Pin 2 of type B
IO-Ports, detected by IO-Link Master
8.6.2 For LioN-P 60 devices
In case of an overload or a short circuit between pin 2 and pin 5 on these ports
(X5 - X8), the following channel-specific diagnostic message is generated:
Channel number of diagnosis
0x05 - 0x08
Channel related diagnosis
code
0x0108
Channel related diagnosis
code message
Short circuit or overload of auxiliary power supply at Pin 2 of type B
IO-Ports, detected by IO-Link Master
8.7 IO-Link C/Q error
If an IO-Link device in COM mode is unplugged, an incorrect IO-Link device
is plugged in, or an electrical fault occurs on the C/Q (Pin 4) line, for example,
due to a short circuit, then following error message is generated:
Manual LioN-P PROFINET IO-Link Master
Version 2.1 10/2017
82