6 Starting operation
6.4 Configuration of the LioN-P
PROFINET I/O modules in STEP 7
6.4.7 Digital input logic
This parameter can be used to configure the logic of channels used as digital
inputs.
Figure 23: Digital input logic
Default setting
NO (Normally Open) for all channels
NO (Normally Open)
A non-damped sensor has an open switching output
(low signal) in this case. The device input detects a low
signal and returns a 0 to the control unit.
NC (Normally Closed)
A non-damped sensor has an closed switching output
(high signal) in this case. The device input detects a
high signal, inverts the signal, and returns a 0 to the
control unit.
Manual LioN-P PROFINET IO-Link Master
Version 2.1 10/2017
49