11.2.2.10.3. Modbus settings for METPOINT
®
SD23
When connecting a METPOINT
®
SD23 via Modbus, the following settings are required:
Step 1: select a free sensor channel
Home
Settings
Sensor settings
Select a free channel (here: channel A1)
Step 2: select Modbus type
Home
Settings
Sensor settings
A1
Type
Modbus and confirm with >OK<.
Step 3: enter a name
Home
Settings
Sensor-settings
A1
Name
Enter a name.
Step 4: define the Modbus settings
Home
Settings
Sensor-settings
A1
right arrow (2. page)
Modbus settings
Notice:
Further information on how to configure the text fields, see chapter „11.2.2.7. Labelling and configuring text fields“ page
The Modbus ID is specified in the data sheet of the
sensor (here: 1).
Adjust the other parameter settings according to the
screenshot.
Step 5: select register
Home
Settings
Sensor-settings
A1
right arrow (2. page)
Va
Use
Proceed in the same manner to select the other
registers.