Installation and Operation Manual
BEKOKAT
®
32 / 88
V01 /11-046
CAUTION
Exceeding or falling below temperatures
If the temperature falls below T <60 °C, T> 200 °C, a warning signal
sounds and the display flashes.
If the temperatures exceed or undershoot the set alarm
temperatures, valves V1 and V2 will be closed at the inlet and
condensate drain of the
BEKOKAT
®
.
In the event of the temperature being undershot, this prevents
untreated compressed air from leaving the system, since catalysis
cannot be reliably carried out at temperatures that are too low.
If the temperature is exceeded, the closing of the inlet and outlet
valves prevents the further supply of compressed air, and therefore
oxygen, and prevents a possible fire.
In addition to the automatic closing of the valves at the inlet and
condensate drain, in this case, the manual shut-off valves must
also be closed before and after the assembly unit.
As soon as the valves close, the potential-free alarm contact is
activated, signalling the fault by means of an external display
(warning signal, light, etc.). This connection option should be used.
If the temperature is exceeded, the system must be shut down and
checked in any case.
Commissioning of the
BEKOKAT
®
is only permitted after
inspection and approval by authorised specialist personnel.