20
the ‘E’ terminal on the terminal block.
Article 250 of the National Electrical Code and enclosures shall be grounded using
The BA364D enclosure is manufactured from conductive plastic per
hubs are fitted to a BA364D, all metallic glands or conduit hubs must be connected
In addition to the supplied bonding plate, when 2 or 3 metallic glands or conduit
with cable glands / conduit hubs selected from the following table
When installed in a hazardous (classified) location the BA364D shall be fitted
Any metallic or plastic cable gland or conduit hub that provides
SSTG-1 STG-1 STAG-1
Permitted gland or conduit hub
Killark Glands
together and grounded.
6.
7.
CAUTION:
CMCXAA050 MCR050 MCX050
Metallic glands and hubs must be grounded – see note 7.
Class I
Class II and III
5.
Class
CHMG-50DT
Crouse – Hinds Myler hubs
the required environmental protection.
O-Z / Gedrey Hubs
MHUB-1
REMKE hub
WH-1-G
NIFW = Nonincendive Field Wiring; any of the wiring methods permitted for unclassified
locations, as defined in the National Electrical Code ANSI/NFPA 70, may be used for
this installation.
8.