17
P1
OPTIONAL
VOLTAGE PULSE,
PROXIMITY DETECTOR
OR SWITCH CONTACT
SEE NOTE 3
OPTIONAL
4/20mA
OUTPUT
C1
C2
INPUT
PULSE
OUPUT
4
3
P2
B2
BACKLIGHT
OPTIONAL
B1
EQUIPMENT
UNCLASSIFIED
LOCATION
REMOTE
RESET
7
8
POWER
SUPPLY
1
2
BA368C
BA364D
HAZARDOUS (CLASSIFIED) LOCATION
UNCLASSIFIED LOCATION
OPTIONAL
ALARM
A1
A2
INPUTS IN HAZARDOUS (CLASSIFIED) LOCATION
ALARM
OPTIONAL
A4
A3
SEE NOTE 1 & 2
BA368C LOCATIONS:
Class I, Division 2, Groups A, B,C, D
Class I, Zone 2, Group IIC
BA364D LOCATIONS:
Class I, Division 2, Groups A, B,C, D
Class II, Division 2, Groups E, F & G
Class III
Class I, Zone 2, Group IIC
or
SEE NOTE 5 & 7
SEE NOTE 4
BA364D & BA368C
Terminals 1 & 2
Vmax = 30V
Ci = 0.02µF
Li = 0.02mH
Terminals 7 & 8
Vmax = 30V dc Voc = 3.8V dc
Ci = 0.02µF Isc = 1.6mA
Li = 0mH Ca = 1000µF
La = 1000mH
Terminals B1 & B2
Vmax = 30V dc
Ci = 0.04µF
Li = 0.03mH
Terminals P1 & P2
Vmax = 30V dc
Ci = 0.02µF
Li = 0.02mH
Terminals C1 & C2
Vmax = 30V dc
Ci = 0.002µF
Li = 0.008mH
Terminals 3 & 4
Vmax = 30V dc Voc = 10.5V dc
Ci = 0.02µF Isc = 9.2mA dc
Li = 0.02mH Ca = 2.39µF
La = 300mH
Terminals 5 & 6
Vmax = 30V dc Voc = 10.5V dc
Ci = 0.02µF Isc = 9.2mA dc
Li = 0.02mH Ca = 2.39µF
La = 300mH
Terminals A1 & A2 and A3 & A4
Vmax = 28V dc
Ci = 0.04µF
Li = 0.03mH
VOLTAGE PULSE,
PROXIMITY DETECTOR
OR SWITCH CONTACT
SEE NOTE 3
6
5
INPUT
SEE
NOTE 7