background image

4.2.5  2-wire proximity detector input

Most  certified  intrinsically  safe  NAMUR  2-wire
proximity  detectors  may  be  directly  connected  to  a
BA314G input, providing the input safety parameters
of the proximity detector are equal to or greater than
the output safety parameters of a BA314G input:

Ui

10.5V dc

Ii

8.2mA dc

Pi

24mW

and the minimum operating voltage of the proximity
detector  is  less  than  7.5V.    The  proximity  detector
must be located in the same hazardous area as the
Tachometer and the associated wiring must be able to
withstand a 500V rms insulation test to earth.

The BA314G contain a configurable debounce circuit
to  prevent  false  triggering  of  the  instrument.  Three
levels of de-bounce protection are  available.
See section 6.6.

4.2.6  Magnetic pick-off input

CoiL

 in the BA314G input configuration menu is a low

level  voltage  pulse  input  intended  for  use  with  an
intrinsically  safe  magnetic  pick-off.    When  a
Tachometer input is configured for 

CoiL

 and terminals

3 & 4 are not linked, input terminals 5 & 6 comply with
the  requirements  for  

simple  apparatus

 allowing

connection to any certified intrinsically safe magnetic
sensor  having  output  parameters  equal  to  or  less
than:

Uo

28V dc

Io

200mA dc

Po

0.84W

The maximum permitted cable parameters will be be
the sensor's Co and Lo specified on it's intrinsic safety
certificate,  less  the  Tachometers  pulse  input
parameters Ci and Li which are small and can often
be ignored.

The  sensor  must  be  located  within  the  same
hazardous  area  as  the  BA314G  and  with  the
associated wiring must be able to withstand a 500V
rms insulation test to earth.

The  BA314G  Tachometer  contains  a  configurable
debounce  circuit  to  prevent  false  triggering.  Three
levels  of  debounce  protection  are  available.    See
section 6.6.

4.2.7  Voltage pulse input

Two voltage  pulse  input  ranges  are independently
selectable in the BA314G Tachometer configuration
menu,  

VoLt5 L

 and  

VoLt5 H

.  When configured for

either of the voltage pulse ranges, and terminals 3 &
4 are not linked, the input terminals 5 & 6 comply
with  the  requirements  for  

simple  apparatus

.   This

allows  the  pulse  input  to  be  connected  to  any
certified  intrinsically  safe  sensor  with  a  voltage
output located within the same hazardous area as
the Tachometer providing it has output parameters
equal to or less than:

Uo

28V dc

Io

200mA dc

Po

0.84W

The BA314G Tachometers may therefore be directly
connected to most certified intrinsically safe sensors
with a high level voltage output.

The   maximum   permitted   cable   parameters   will   be
defined by the sensor's intrinsic safety Co and Lo
less the Tachometer's pulse input parameters Ci and
Li which are small and can often be ignored.

The BA314G contain a configurable debounce circuit
to prevent false triggering of the instrument. Three
levels of de-bounce protection are  available.
See section 6.6.

4.2.8  Remote reset

The Tachometer's run-time display may be remotely
reset to zero by connecting terminals RS1 and RS2
together  for  more  than  one  second.  Permanent
interconnection inhibits the run-time clock.  Remote
resetting may be accomplished by any mechanically
operated switch located in the same hazardous area
as  the  Tachometer  providing  the  switch  and  the
associated  wiring  can  withstand  a  500V  rms
insulation  test  to  earth.    No  galvanic  isolator  is
required.

A BA314G may also be remotely reset from the safe
area.      Any  switch  may  be  used  but  a  galvanic
isolator  is  required  to  transfer  the  contact  closure
into  the  hazardous  area.    Fig  4  illustrates  how  a
BA314G may be reset from both the safe and the
hazardous area.

Note:

  The  BA314G  Tachometer  may  be

configured to reset the total display to zero
by operating the  

&

 and

  *

 push buttons

simultaneously for more than two seconds
in  the  totalising  mode  i.e.  when  the
instrument is displaying flow.    See 6.15

14

Summary of Contents for BA314E

Page 1: ...Issue 1 7th February 2017 BA314G and BA314E Intrinsically safe Tachometers Issue 1...

Page 2: ...ns 6 3 Summary of configuration functions 6 4 Input inPut 6 5 Input type inP tYPE 6 6 Debounce dEbouncE 6 7 Display update interval uPdAtE 6 8 Run time display di5P 2 6 9 Position of the decimal point...

Page 3: ...time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Intrinsic safety 9 4 2 System design 9...

Page 4: ...4...

Page 5: ...A314E only has ATEX gas certification The main sections of this manual describe ATEX gas certification For international applications the BA314G and BA314E also have IECEx certification which is descr...

Page 6: ...fitted A Dual alarm outputs P Pulse output Fitted to all BA314G C 4 20mA output Access to configuration menu Note When optional alarms are fitted the Tachometer may be configured to provide direct acc...

Page 7: ...rt time Be used with gases in groups Group A propane Group B ethylene Group C hydrogen In gases that may be used with equipment having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135...

Page 8: ...Po 0 84W or complies with requirements for simple apparatus b The Sensor and associated wiring can withstand a 500V rms insulation test to earth c The Sensor is located in the same hazardous area as t...

Page 9: ...enclosure It shows the ATEX IECEx and ETL certification information plus BEKA associates name location year of manufacture and the instrument serial number Other certification information may also be...

Page 10: ...barrier the supply voltage in the safe area must be between 15 5V and the maximum working voltage of the Zener barrier which depending upon manufacturer will be approximately 26V Note The optional fac...

Page 11: ...4 1 6 Magnetic pick off input Sensors incorporating a magnetic pick off to sense movement will have a low level voltage output unless the sensor incorporates an amplifier CoiL in the BA314G input conf...

Page 12: ...usly for more than two seconds in the totalising mode i e when the instrument is displaying flow See section 6 15 4 2 Use with Galvanic Isolators Galvanic isolators are probably the simplest intrinsic...

Page 13: ...ector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0V Magnetic pick off 0mV 40mV peak Proximity detector 1 2mA 2 1mA Switch 100 1000 Switch contacts proximity detectors and open colle...

Page 14: ...ge pulse input ranges are independently selectable in the BA314G Tachometer configuration menu VoLt5 L and VoLt5 H When configured for either of the voltage pulse ranges and terminals 3 4 are not link...

Page 15: ...tor An insulated M4 stud is provided in the bottom right hand corner the back box for interconnecting cable screens The BA314G Tachometer may be pipe mounted using a BA393G pipe mounting kit or panel...

Page 16: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as an...

Page 17: ...tor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the monitor...

Page 18: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 19: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 20: ...20...

Page 21: ...21...

Page 22: ...Tachometer miscounting when the input pulse has noisy edges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounc...

Page 23: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 24: ...d it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thresho...

Page 25: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Page 26: ...g 11 shows how a 2 channel Zener barrier may be used to produce a voltage pulse in the safe area that could be used to drive a safe area tachometer The positive terminal of the pulse output circuit P1...

Page 27: ...e output pulse with defined duration by the diVidE and durAtion functions Using the or push button select 5ourCE in the pulse output sub menu and press to reveal the existing pulse source The source c...

Page 28: ...ng the or push button to select the required value followed by the button to return to durAtion prompt Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ourC...

Page 29: ...between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 second...

Page 30: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 31: ...ts unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the se...

Page 32: ...tion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installe...

Page 33: ...an be supplied with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low funct...

Page 34: ...r barrier or galvanic isolator providing the output parameters of the circuit do not exceed Uo 28V dc Io 200mA Po 0 84W The maximum equivalent capacitance and inductance between each set of alarm term...

Page 35: ...nt Note 5P15 is displayed for a speed alarm and 5P1H for a run time alarm See section 9 3 6 HI LO Alarm function Defines whether the alarm has a high or low function See section 9 3 7 Display Summary...

Page 36: ...36...

Page 37: ...turn to the Hi Lo prompt in the alarm sub menu 9 3 8 Alarm output status no nC Each single pole alarm output may be open or closed in the non alarm condition When the BA314G or BA318E power supply is...

Page 38: ...ts without having access to the configuration and alarm sub menus Protection against unauthorised or accidental adjustment is provided by a separate security access code Using the or push button selec...

Page 39: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 40: ...e not powered but it is totally isolated from all other Tachometer circuits It is effectively a 2 wire 4 20mA transmitter requiring a minimum supply of 5V with its current being controlled by the Tac...

Page 41: ...adjust the flashing digit and the button to transfer control to the next digit When set as required press to enter the value and return to the 4 000 prompt in the 4 20mA output sub menu 9 4 7 Display...

Page 42: ...ersist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust layer...

Page 43: ...tification codes Ex ia IIC T5 Ga Ta 40 C to 70 C Ex ia IIIC T80 C IP66 Da Ta 40 C to 60 C The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety parameters descr...

Page 44: ...parameters the systems shown in sections 3 and 4 of this manual may therefore also be used for US and Canadian installations subject to compliance with the local codes of practice ETL and cETL intrin...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...48...

Page 49: ...49...

Page 50: ...50...

Page 51: ...51...

Page 52: ...52...

Page 53: ...53...

Page 54: ...54...

Page 55: ...55...

Page 56: ...56...

Page 57: ...he two mounting holes are located in a separate compartment with a sealed cover allowing the instrument to be installed without exposing the display assembly The enclosure is fitted with a bonding pla...

Page 58: ...d one or both of the IP66 stopping plugs may be replaced with an appropriate IP rated cable gland or conduit fitting d Connect the field wiring to the terminals as shown in Fig A4 2 7 Replace the inst...

Reviews: