background image

The  second  digit  defines  the  deviation  from  the
displayed speed at which the filtering defined by the
first digit will be overridden and the Tachometer speed
display will move rapidly to the new value.

Second

digit

Magnitude of input
step change which

will override the filter
and move the speed
display rapidly to the

new value..

X0

              Off

X1

              1%

X2

              2%

X3

              4%

X4

              8%

X5

            12%

X6

            16%

X7

            24%

X8

            32%

X9

            64%

By careful adjustment of the two parameters a stable
display with an acceptable input step response can be
obtained for most applications.

During commissioning it is recommended that initially
the second digit is set to 0 (off) and the first digit is
adjusted to provide an acceptable Tachometer display
stability. The second digit should then be increased
until the selected step size is greater than the noise
on the display, at which setting the Tachometer speed
display will become stable.  These will be the optimum
filter  parameters  for  acceptable  Tachometer  speed
display stability and a fast response to a large speed
change of the monitored machinery.

To  check  or  change  the  filter  select  

FiLtEr

 in  the

configuration menu and press 

(

 

which will reveal the

current settings with the first digit flashing. 

 

 Pressing

the 

& or *

 button will change the flashing digit and

(

  will  transfer  control  to  the  second  digit.    While

making adjustments the filtered Tachometer display is
shown on the lower display in place of run-time so that
stability can be assessed while adjustments are being
made.  When set as required, press the 

button to

enter the revised parameters and return to the 

FiLtEr

prompt in the configuration menu.

6.13  Clip-off:  

CLP  oFF

Clip-off determines the displayed speed at which the
run-time  counter  starts  to  function,  below  this
threshold the run-time counter does not function.   If
the run-time counter is required to operate whenever
the Tachometer is powered, clip-off should be set to
zero.

If  the  run-time  display  is  not  being  used  it  is  not
necessary to enter a clip-off value - see 6.8.

To  check  or  change  the  clip-off  threshold  select

CLP  oFF

  from  the  configuration  menu  and  press

(

  which  will  reveal  the  current  setting.    The

threshold is shown in the units already selected for
the Tachometer speed display with one digit flashing.
The value of the flashing digit may be adjusted by
pressing the 

&

 or 

*

 button, when set as required

pressing  

(

  will  transfer  control  to  the  next  digit.

When all the digits have been adjusted, press the

)

 

 

button to enter the revised threshold and return

to the 

CLP oFF

 prompt in the configuration menu.

When the Tachometer speed display falls below the
clip-off  threshold,  the  HOLD  annunciator  will  be
activated and the run-time clock will be stopped.

Note:

To  avoid  confusion,

 

when  the  speed  scale

factor  

5CALE

 

.

 

5

,  timebase   

t-bA5E

,  or the

position of the speed

 

display decimal point 

dp

are  changed,  clip-off  will  automatically  be
reset to zero.  A new clip-off threshold must be
entered after any of these changes have been
made.

6.14  Local reset:  

LoC clr

The Local reset function contains two sub-functions

clr tot

 and 

clr gtot

 which when enabled allow the

run-time display and grand total run-time to be reset
to  zero  via  the  instrument  push  buttons  while  the
Tachometer is in the display mode.

6.15  Local run-time reset:  

clr tot

clr tot

  is  a  sub-menu  in  the  LoC

 clr 

 function

which when activated allows an operator to reset the
run-time display to zero while the Tachometer is in
the display mode by operating the  

&

  &  

*

 push

buttons simultaneously for more than three seconds.

Select 

LoC clr

 in the configuration menu and press

which will reveal the 

clr tot

 prompt, operate 

(

again which will show

 

if the local run-time reset is 

on

or  

oFF

.   If set as required operate the  

)  

button

twice to return to the configuration menu, or the 

&

or  

*

 button to change the setting followed by the

)  

button twice to enter the change and return to

the 

LoC

  

clr

 prompt in the configuration menu.

Note:

The run-time display may also be reset to zero
remotely  by  connecting  terminals  RS1  and
RS2 together for more than one second.  See
sections 3.5;   4.1.8 and 4.2.8 of this manual.

24

Summary of Contents for BA314E

Page 1: ...Issue 1 7th February 2017 BA314G and BA314E Intrinsically safe Tachometers Issue 1...

Page 2: ...ns 6 3 Summary of configuration functions 6 4 Input inPut 6 5 Input type inP tYPE 6 6 Debounce dEbouncE 6 7 Display update interval uPdAtE 6 8 Run time display di5P 2 6 9 Position of the decimal point...

Page 3: ...time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Intrinsic safety 9 4 2 System design 9...

Page 4: ...4...

Page 5: ...A314E only has ATEX gas certification The main sections of this manual describe ATEX gas certification For international applications the BA314G and BA314E also have IECEx certification which is descr...

Page 6: ...fitted A Dual alarm outputs P Pulse output Fitted to all BA314G C 4 20mA output Access to configuration menu Note When optional alarms are fitted the Tachometer may be configured to provide direct acc...

Page 7: ...rt time Be used with gases in groups Group A propane Group B ethylene Group C hydrogen In gases that may be used with equipment having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135...

Page 8: ...Po 0 84W or complies with requirements for simple apparatus b The Sensor and associated wiring can withstand a 500V rms insulation test to earth c The Sensor is located in the same hazardous area as t...

Page 9: ...enclosure It shows the ATEX IECEx and ETL certification information plus BEKA associates name location year of manufacture and the instrument serial number Other certification information may also be...

Page 10: ...barrier the supply voltage in the safe area must be between 15 5V and the maximum working voltage of the Zener barrier which depending upon manufacturer will be approximately 26V Note The optional fac...

Page 11: ...4 1 6 Magnetic pick off input Sensors incorporating a magnetic pick off to sense movement will have a low level voltage output unless the sensor incorporates an amplifier CoiL in the BA314G input conf...

Page 12: ...usly for more than two seconds in the totalising mode i e when the instrument is displaying flow See section 6 15 4 2 Use with Galvanic Isolators Galvanic isolators are probably the simplest intrinsic...

Page 13: ...ector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0V Magnetic pick off 0mV 40mV peak Proximity detector 1 2mA 2 1mA Switch 100 1000 Switch contacts proximity detectors and open colle...

Page 14: ...ge pulse input ranges are independently selectable in the BA314G Tachometer configuration menu VoLt5 L and VoLt5 H When configured for either of the voltage pulse ranges and terminals 3 4 are not link...

Page 15: ...tor An insulated M4 stud is provided in the bottom right hand corner the back box for interconnecting cable screens The BA314G Tachometer may be pipe mounted using a BA393G pipe mounting kit or panel...

Page 16: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as an...

Page 17: ...tor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the monitor...

Page 18: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Page 19: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Page 20: ...20...

Page 21: ...21...

Page 22: ...Tachometer miscounting when the input pulse has noisy edges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounc...

Page 23: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Page 24: ...d it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thresho...

Page 25: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Page 26: ...g 11 shows how a 2 channel Zener barrier may be used to produce a voltage pulse in the safe area that could be used to drive a safe area tachometer The positive terminal of the pulse output circuit P1...

Page 27: ...e output pulse with defined duration by the diVidE and durAtion functions Using the or push button select 5ourCE in the pulse output sub menu and press to reveal the existing pulse source The source c...

Page 28: ...ng the or push button to select the required value followed by the button to return to durAtion prompt Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ourC...

Page 29: ...between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 second...

Page 30: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Page 31: ...ts unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the se...

Page 32: ...tion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installe...

Page 33: ...an be supplied with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low funct...

Page 34: ...r barrier or galvanic isolator providing the output parameters of the circuit do not exceed Uo 28V dc Io 200mA Po 0 84W The maximum equivalent capacitance and inductance between each set of alarm term...

Page 35: ...nt Note 5P15 is displayed for a speed alarm and 5P1H for a run time alarm See section 9 3 6 HI LO Alarm function Defines whether the alarm has a high or low function See section 9 3 7 Display Summary...

Page 36: ...36...

Page 37: ...turn to the Hi Lo prompt in the alarm sub menu 9 3 8 Alarm output status no nC Each single pole alarm output may be open or closed in the non alarm condition When the BA314G or BA318E power supply is...

Page 38: ...ts without having access to the configuration and alarm sub menus Protection against unauthorised or accidental adjustment is provided by a separate security access code Using the or push button selec...

Page 39: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Page 40: ...e not powered but it is totally isolated from all other Tachometer circuits It is effectively a 2 wire 4 20mA transmitter requiring a minimum supply of 5V with its current being controlled by the Tac...

Page 41: ...adjust the flashing digit and the button to transfer control to the next digit When set as required press to enter the value and return to the 4 000 prompt in the 4 20mA output sub menu 9 4 7 Display...

Page 42: ...ersist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust layer...

Page 43: ...tification codes Ex ia IIC T5 Ga Ta 40 C to 70 C Ex ia IIIC T80 C IP66 Da Ta 40 C to 60 C The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety parameters descr...

Page 44: ...parameters the systems shown in sections 3 and 4 of this manual may therefore also be used for US and Canadian installations subject to compliance with the local codes of practice ETL and cETL intrin...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...48...

Page 49: ...49...

Page 50: ...50...

Page 51: ...51...

Page 52: ...52...

Page 53: ...53...

Page 54: ...54...

Page 55: ...55...

Page 56: ...56...

Page 57: ...he two mounting holes are located in a separate compartment with a sealed cover allowing the instrument to be installed without exposing the display assembly The enclosure is fitted with a bonding pla...

Page 58: ...d one or both of the IP66 stopping plugs may be replaced with an appropriate IP rated cable gland or conduit fitting d Connect the field wiring to the terminals as shown in Fig A4 2 7 Replace the inst...

Reviews: