background image

27

Fig 17 Setpoint adjustment from the display mode

To adjust an alarm setpoint select

5P1

or

5P2

and

press

(

which will reveal the current setting.

Each digit of the setpoint may be adjusted using
the

&

and

*

push buttons, and the

(

button to

move control to the next digit. When the required
setpoint has been entered, pressing

)

will return

the display to the

5P1

or

5P2

prompt from which the

other setpoint may be selected, or the indicator
may be returned to the display mode by pressing

)

 again.

Note: With the indicator in the display mode, direct
access to the alarm setpoints is only available
when the

AC5P

menu is enabled - see section

9.3.12

9.3.14 Displaying setpoints on BA324G and

BA324G-SS bargraph

One of the selectable bargraph formats

Alr5P

allows a low or a high setpoint plus the displayed
value to be represented, or a low and a high
setpoint plus the displayed value to be represented
by the bargraph as shown in Fig 18.

Fig 18  Displayed value and setpoints on bargraph

The bargraph area below the low alarm setpoint
and the area above the high alarm setpoint are
activated.

The displayed variable is represented

by an activated bar which moves between these
low and high alarm setpoints.

When the activated bar representing the displayed
variable is adjacent to the area representing the
low or high alarm setpoints, the bar flashes.
When a displayed variable equals the low or high
alarm the complete bargraph representing the
activated alarm flashes irrespective of whether the
alarm output has been delayed or cleared.

For this function to operate

5P1

must be

conditioned as a low alarm and

5P2

as a high

alarm;

5P1

must always be less than

5P2

.

Incorrect configuration is shown by a flashing
bargraph scale with no activated bars.

Summary of Contents for BA304G

Page 1: ...Issue 5 19th September 2018 BA304G BA304G SS BA324G BA324G SS intrinsically safe loop powered field mounting indicators Issue 5...

Page 2: ...to a new indicator 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine ma...

Page 3: ...sting and Certification Ltd and comply with the European ATEX Directive 2014 34 EU The EC Type Examination certificate specifies that under fault conditions the output voltage current and power at the...

Page 4: ...d Body Intertek Testing and Certification Ltd have issued all the models with a common EC Type Examination Certificate number ITS11ATEX27253X This confirms compliance with harmonised European standard...

Page 5: ...face of the instrument assembly It shows the ATEX and IECEx certification information and BEKA associates name and location Non European certification information may also be shown The instrument seri...

Page 6: ...sufficient to drive the indicator plus the interface When a high integrity earth connection is already available a Zener barrier is usually the least expensive option If an earth connection is not ava...

Page 7: ...ing cable screens If field wiring is to be terminated prior to the installation of the indicator assembly the GRP models BA304G and BA324G can be supplied with an optional back box terminal assembly w...

Page 8: ...for joining cable screens 5 6 Units of measurement and tag marking on scale card The indicator s units of measurement and tag information are shown on a scale card which slides into the indicator New...

Page 9: ...e card carefully insert it into the slot on the right hand side of the input terminals as shown in Fig 6b Force should be applied evenly to both sides of the scale card to prevent it twisting The card...

Page 10: ...A324G BA304G SS BA324G SS Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA 2ero 0 0 0 00 Display at 20mA 5PAn 100 0 100 00 Resolution rE5n 1 digit 1 digit Bargraph start BarLo 0 0...

Page 11: ...11...

Page 12: ...Lin 16 segment adjustable lineariser To reveal the indicator s existing function select FunC from the configuration menu and press If the function is set as required press to return to the menu or pre...

Page 13: ...e two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrumen...

Page 14: ...on and oFF When set as required press to return to the tARE prompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit securi...

Page 15: ...ws direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows d...

Page 16: ...16...

Page 17: ...g break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function de...

Page 18: ...pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press which wi...

Page 19: ...ertificate is available If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it is recommended that th...

Page 20: ...ered the backlight produces green background illumination enabling the display to be read at night or in poor lighting conditions No additional power supply intrinsic safety interface or field wiring...

Page 21: ...rgency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently configured as a high or low alarm with a norma...

Page 22: ...simple apparatus This simplifies system documentation and allows the alarm output terminals 8 9 and 10 11 to be connected to almost any intrinsically safe circuit protected by a Zener barrier or galv...

Page 23: ...23...

Page 24: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 25: ...for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pre...

Page 26: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 27: ...tpoint plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bar...

Page 28: ...d into a panel aperture The kit provides an IP66 seal between the indicator and the instrument panel it is therefore suitable for mounting a stainless steel indicator in a sealed panel enclosure 9 6 B...

Page 29: ...nly persist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust l...

Page 30: ...cifies the following certification codes Ex ia IIC T5 Ga Ex ia IIIC T80 C Da IP66 Ta 40 C to 70 C The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety paramete...

Page 31: ...70 C CL II Div 1 Groups E F G 40 C Ta 60 C CL III Div 1 40 C Ta 60 C USA Zone classification CL I Zone 0 AEx ia IIC T5 Ga 40 C Ta 70 C Zone 20 AEx ia IIIC T80 C Da 40 C Ta 60 C Canada Zone classificat...

Page 32: ...32...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36...

Page 37: ...37...

Page 38: ...38...

Page 39: ...39...

Reviews: