background image

14

The indicator’s digital display at which the
bargraph starts is defined by the

bArLo

sub-

function which is selected by pressing the

*

button followed by the

(

button which will reveal

the current indicator display at which the bargraph
starts.

The flashing digit can be adjusted by

pressing the

&

or

*

buttons, when set as

required pressing

(

will transfer control to the

next digit. When all the digits have been adjusted,
press

)

to return to the

bArLo

prompt from which

bArHi

which defines the finishing point of the

bargraph can be selected by pressing the

*

button.

bArHi

is adjusted in the same way as

bArLo

. When set as required, pressing

)

twice

will return the display to the

bAr

prompt in the

configuration menu.

Note:

bArLo

must be set lower than

bArHi

,

incorrect setting is indicated by the bargraph scale
flashing with a single bargraph segment activated.

6.8

Function of the 

(

 push-button:  

C--P

When the indicator is in the display mode,
operating the

(

push button will display the input

current in milliamps, or the displayed value as a
percentage

of

the

difference

between

the

displayed values at 4mA and 20mA inputs.

To check or change the function of the

(

push

button select

C--P

from the configuration menu

and press

(

to reveal the current setting.

Pressing the

&

or

*

button will toggle the setting

between

4-20

the current display in milliamps and

PC

the percentage display. When set as required

press

)

to return to the

C--P

prompt in the

configuration menu.

6.9

Tare function:  

tArE

The tare function is primarily intended for use with
a weighing system. When the indicator is in the
display mode and the tare function is activated,
pressing the

)

button for more than three

seconds will zero the indicator’s digital display and
activate the tare annunciator. On the BA324G and
BA324G-SS, the bargraph remains linked to the
digital display when the tare function is activated.
Subsequent operation of the

)

push button for

less than 3 seconds will return the indicator to the
gross display and deactivate the tare annunciator.

To check or change the tare function select

tARE

from the configuration menu and press

(

to

reveal the current setting. Pressing the

&

or

*

button will toggle the setting between

on

and

oFF

.

When set as required press

)

to return to the

tARE

 prompt in the configuration menu.

6.10

Security code:  

CodE

Access to the instrument configuration menu may
be protected by a four digit security code which

must be entered to gain access. New instruments
are configured with the default security code

0000

which

allows

unrestricted

access

to

all

configuration functions.

To enter a new security code select

CodE

from the

configuration menu and press

(

which will cause

the indicator to display the existing security code
with one digit flashing. The flashing digit can be
adjusted using the

&

or

*

push buttons, when

set as required operating the

(

button will

transfer control to the next digit.

When all the

digits have been adjusted press

)

to return to the

CodE

prompt in the configuration menu. The

revised security code will be activated when the
indicator is returned to the display mode. Please
contact BEKA associates sales department if the
security code is lost.

6.11

Reset to factory defaults:  

r5Et

This function enables the indicator and the
lineariser to be quickly returned to the factory
default configurations shown in sections 6.0 and
7.4.

To reset the indicator or lineariser select

r5Et

from

the configuration menu and press

(

, the indicator

will display one of the reset options 

ConF

 or 

LtAb

.

ConF

Resets the indicator to defaults

LtAb

Resets the lineariser to defaults

Using the

&

or

*

push button select the

required sub-function and press

(

. To prevent

accidental resetting the request must be confirmed
by entering

5urE

. Using the

*

button set the first

flashing digit to

5

and press

(

to transfer control

to the second digit which should be set to

u

.

When

5urE

has been entered pressing the

)

button will reset the selected configuration menus
and return the display to the

r5Et

function in the

configuration menu.

6.12

Under and over-range

If the numerical display range of the indicator is
exceeded, all the decimal points will flash as
shown below:

 BA304G

 BA324G

                                     BA304G-SS       BA324G-SS

Underrange

-9

 

.

 

9

 

.

 

9

 

.

 

9

-9

 

.

 

9

 

.

 

9

 

.

 

9

 

.

 

9

Overrange

9

 

.

 

9

 

.

 

9

 

.

 

9

 

9

 

.

 

9

 

.

 

9

 

.

 

9

 

.

 

9

Although not guaranteed, most indicators will
continue to function normally with an input current
between 1.8mA and 4mA, at lower currents the
instrument will display

LPLo

before it stops

functioning.

Under or over-range of the BA324G and the
BA324G-SS bargraph is indicated by a flashing
arrow at the appropriate end of the bargraph.

Summary of Contents for BA304G

Page 1: ...Issue 5 19th September 2018 BA304G BA304G SS BA324G BA324G SS intrinsically safe loop powered field mounting indicators Issue 5...

Page 2: ...to a new indicator 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine ma...

Page 3: ...sting and Certification Ltd and comply with the European ATEX Directive 2014 34 EU The EC Type Examination certificate specifies that under fault conditions the output voltage current and power at the...

Page 4: ...d Body Intertek Testing and Certification Ltd have issued all the models with a common EC Type Examination Certificate number ITS11ATEX27253X This confirms compliance with harmonised European standard...

Page 5: ...face of the instrument assembly It shows the ATEX and IECEx certification information and BEKA associates name and location Non European certification information may also be shown The instrument seri...

Page 6: ...sufficient to drive the indicator plus the interface When a high integrity earth connection is already available a Zener barrier is usually the least expensive option If an earth connection is not ava...

Page 7: ...ing cable screens If field wiring is to be terminated prior to the installation of the indicator assembly the GRP models BA304G and BA324G can be supplied with an optional back box terminal assembly w...

Page 8: ...for joining cable screens 5 6 Units of measurement and tag marking on scale card The indicator s units of measurement and tag information are shown on a scale card which slides into the indicator New...

Page 9: ...e card carefully insert it into the slot on the right hand side of the input terminals as shown in Fig 6b Force should be applied evenly to both sides of the scale card to prevent it twisting The card...

Page 10: ...A324G BA304G SS BA324G SS Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA 2ero 0 0 0 00 Display at 20mA 5PAn 100 0 100 00 Resolution rE5n 1 digit 1 digit Bargraph start BarLo 0 0...

Page 11: ...11...

Page 12: ...Lin 16 segment adjustable lineariser To reveal the indicator s existing function select FunC from the configuration menu and press If the function is set as required press to return to the menu or pre...

Page 13: ...e two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrumen...

Page 14: ...on and oFF When set as required press to return to the tARE prompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit securi...

Page 15: ...ws direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows d...

Page 16: ...16...

Page 17: ...g break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function de...

Page 18: ...pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press which wi...

Page 19: ...ertificate is available If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it is recommended that th...

Page 20: ...ered the backlight produces green background illumination enabling the display to be read at night or in poor lighting conditions No additional power supply intrinsic safety interface or field wiring...

Page 21: ...rgency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently configured as a high or low alarm with a norma...

Page 22: ...simple apparatus This simplifies system documentation and allows the alarm output terminals 8 9 and 10 11 to be connected to almost any intrinsically safe circuit protected by a Zener barrier or galv...

Page 23: ...23...

Page 24: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 25: ...for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pre...

Page 26: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 27: ...tpoint plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bar...

Page 28: ...d into a panel aperture The kit provides an IP66 seal between the indicator and the instrument panel it is therefore suitable for mounting a stainless steel indicator in a sealed panel enclosure 9 6 B...

Page 29: ...nly persist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust l...

Page 30: ...cifies the following certification codes Ex ia IIC T5 Ga Ex ia IIIC T80 C Da IP66 Ta 40 C to 70 C The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety paramete...

Page 31: ...70 C CL II Div 1 Groups E F G 40 C Ta 60 C CL III Div 1 40 C Ta 60 C USA Zone classification CL I Zone 0 AEx ia IIC T5 Ga 40 C Ta 70 C Zone 20 AEx ia IIIC T80 C Da 40 C Ta 60 C Canada Zone classificat...

Page 32: ...32...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36...

Page 37: ...37...

Page 38: ...38...

Page 39: ...39...

Reviews: