7.

LINEARISER

A sixteen segment, seventeen break-point (0 to 16)
lineariser may be selected in the

FunC

section of

the configuration menu.

The position of each

break-point is fully adjustable so that the slope of
the straight line between break-points can be set to
compensate for input non-linearity, thus allowing
the indicator to display

non-linear process

variables in linear engineering units. Each break-
point must occur at a current greater than the
preceding break-point and less than the following
break-point, in the range 3.8 to 21.0mA. If this
requirement is not observed when configuring the
lineariser the indicator will display

FaiL

and the

configuration adjustment which produced the error
message will be ignored. Fig 8 shows a typical
linearised indicator characteristic.

Fig 8 shows a typical linearising characteristic

Selecting

Lin

in the

FunC

section of the

configuration menu activates the lineariser, this
does not change the configuration menu shown in
Fig 7, but the

CAL

and

5Et

functions are extended

as shown in Fig 9. As with a linear indicator,
calibration of the lineariser may be performed with
an external current source using the

CAL

function,

or with the internal reference using the

5Et

function.

The lineariser calibration is retained irrespective of
how the indicator function

FunC

is subsequently

changed. It is therefore possible to select and
deselect

the

lineariser

without

having

to

reconfigure it each time.

The lineariser calibration may be reset to the
factory default settings without changing the
indicator configure using the

LtAb

function

described in section 6.11.

7.1

Lineariser calibration using an external
current source.

This method allows direct calibration of the
lineariser with an external current source and is
the preferred method when traceability is required.
If the exact system non-linearity is unknown, this
method also allows direct calibration from the
variable to be displayed. e.g. the output from a
level sensor in an irregular tank may be displayed
in linear volumetric units by filling the tank with
known incremental volumes and calibrating the
indicator to display the sum of the increments at
each break-point.

The number of break-point required should first be
entered using the

Add

and

dEL

functions. In both

these sub-functions the indicator initially displays
the current break-point and the total number of
break-points being used as shown below.

   Display

      Summary of function              

Add

Add a break-point

Adds a new break-point before the
displayed break-point. The calibration of
existing break-points is not changed, but
the

identification

number

of

all

subsequent break-points is increased by
one.

dEL

Remove a break-point

Removes the displayed break-point and
joins the preceding break-point to the
following break-point with a straight line.
The

identification

number

of

all

subsequent break-points is decreased by
one.

To add a break-points use the

&

or

*

button to

select

CAL

from the configuration menu and press

(

which will result in the

Add

sub-function prompt

being displayed. To enter the sub-function press

(

which will reveal the current break-point and

the total number of break-points which have
already been entered. When adding a break-point
the insertion position can be selected using the

&

and

*

push buttons followed by

(

push button

to insert the additional break-point. In previously
uncalibrated linearisers each new break-point
should be added in front of the highest existing
break-point, if this sequence is not followed a

FaiL

message will occur in the

Pt5

function.

See

example in section 7.1.1.

Summary of Contents for BA304G

Page 1: ...Issue 5 19th September 2018 BA304G BA304G SS BA324G BA324G SS intrinsically safe loop powered field mounting indicators Issue 5...

Page 2: ...to a new indicator 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine ma...

Page 3: ...sting and Certification Ltd and comply with the European ATEX Directive 2014 34 EU The EC Type Examination certificate specifies that under fault conditions the output voltage current and power at the...

Page 4: ...d Body Intertek Testing and Certification Ltd have issued all the models with a common EC Type Examination Certificate number ITS11ATEX27253X This confirms compliance with harmonised European standard...

Page 5: ...face of the instrument assembly It shows the ATEX and IECEx certification information and BEKA associates name and location Non European certification information may also be shown The instrument seri...

Page 6: ...sufficient to drive the indicator plus the interface When a high integrity earth connection is already available a Zener barrier is usually the least expensive option If an earth connection is not ava...

Page 7: ...ing cable screens If field wiring is to be terminated prior to the installation of the indicator assembly the GRP models BA304G and BA324G can be supplied with an optional back box terminal assembly w...

Page 8: ...for joining cable screens 5 6 Units of measurement and tag marking on scale card The indicator s units of measurement and tag information are shown on a scale card which slides into the indicator New...

Page 9: ...e card carefully insert it into the slot on the right hand side of the input terminals as shown in Fig 6b Force should be applied evenly to both sides of the scale card to prevent it twisting The card...

Page 10: ...A324G BA304G SS BA324G SS Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA 2ero 0 0 0 00 Display at 20mA 5PAn 100 0 100 00 Resolution rE5n 1 digit 1 digit Bargraph start BarLo 0 0...

Page 11: ...11...

Page 12: ...Lin 16 segment adjustable lineariser To reveal the indicator s existing function select FunC from the configuration menu and press If the function is set as required press to return to the menu or pre...

Page 13: ...e two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrumen...

Page 14: ...on and oFF When set as required press to return to the tARE prompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit securi...

Page 15: ...ws direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows d...

Page 16: ...16...

Page 17: ...g break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function de...

Page 18: ...pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press which wi...

Page 19: ...ertificate is available If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it is recommended that th...

Page 20: ...ered the backlight produces green background illumination enabling the display to be read at night or in poor lighting conditions No additional power supply intrinsic safety interface or field wiring...

Page 21: ...rgency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently configured as a high or low alarm with a norma...

Page 22: ...simple apparatus This simplifies system documentation and allows the alarm output terminals 8 9 and 10 11 to be connected to almost any intrinsically safe circuit protected by a Zener barrier or galv...

Page 23: ...23...

Page 24: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 25: ...for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pre...

Page 26: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 27: ...tpoint plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bar...

Page 28: ...d into a panel aperture The kit provides an IP66 seal between the indicator and the instrument panel it is therefore suitable for mounting a stainless steel indicator in a sealed panel enclosure 9 6 B...

Page 29: ...nly persist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust l...

Page 30: ...cifies the following certification codes Ex ia IIC T5 Ga Ex ia IIIC T80 C Da IP66 Ta 40 C to 70 C The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety paramete...

Page 31: ...70 C CL II Div 1 Groups E F G 40 C Ta 60 C CL III Div 1 40 C Ta 60 C USA Zone classification CL I Zone 0 AEx ia IIC T5 Ga 40 C Ta 70 C Zone 20 AEx ia IIIC T80 C Da 40 C Ta 60 C Canada Zone classificat...

Page 32: ...32...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36...

Page 37: ...37...

Page 38: ...38...

Page 39: ...39...

Reviews: