Attention!!
The  regulations  described  in  this  paragraph  must  performed  be  authorized  and  specialized  technician  are
suceptibile  to  compromise  the  safety  of  the  survey.

If  the  device  does  not  start  up.
Check  that  the  12/24  Vdc  power  is  present,  and  that  positive  and  negative  polarity  has  not  been  inverted.

If  the  Fault  LED  lights  up.
Check  that  the  cables  are  connected  according  to  the  drawing,  and  that  the  wire  isolation  sheath  has  not  been
pinched.
Check  the  voltage  at  the  terminals  1-2.  It  must  be  higher  than  10,80  Vdc  and  lesser  than  26,4  Vdc.
Check  that  the  connector  of  the  sensor  is  correctly  inserted.

If  it’s  connected  to  control  unit.  Check  the  voltage  at  the  terminals  2-3.  It  must  be  from  a  minimum  of
0.8  Vdc  to  a  maximum  of  1.1  Vdc.

Remark.
If  the probes  are connected  to  the control  units    BX308 and  BX316  the  voltage  at  the  terminals  2  and 3  must
be  from  a  minimum  of  0.6  to  a  maximum  of  0.75  VDC

If   othe r  p rob le ms  arise ,  a  sp e cialise d   and /or  authorise d   te chnician  and /or  the   Distrib utor  of
BEINAT S.r.l. should be contacted directly.

WARNING.

These  measurement  should  be  performed  in
clean  air.

Moreover,  this  test  must  be  performed  only
with  the  probe  connected  to  a  control  unit,  or
with  a  220  Ohm  resistance  installed  between
terminal  2  and  terminal  3.

.

Linear  Otput  4-20  mA

3    2    1

R

0

1

3

2

1,1

VDC

Voltmeter

Power  Supply
    12÷24  V.

Troubleshooting before  calling  a  technician

Display legend

Displays  the  type  of  probe  or  device
Displays  the  serial  number
Displays  the  week  and  year  of  manufacture
Displays  tth e  remaini ng  days  a t  th e  end  of  the
operating  cycle.
Displays  how  many  times  the  probe  has  been  turned
o n .
Displays  how  many  times  is  gone  into  alarm.
Displays  how  many  corrections  have  been  done
Displays  the operating  range  if  at  20  or  at  100% of  LEL
Displays  a  scrolling  to  the  normalized  value,  coming
out  of  the  gas  cap,  modifying  these  data  compromises
th e  f u n cti o n i n g  a n d  i s  reserved  f o r  a u th o ri zed
technicians.

Operation  of  the  TS1008  Tester
By  connecting  the  TS1008  tester,  you  can  proceed  to  check  the  probe  in  question  and  print  the  test  report.

ADC  80  16  (125  145)
probe  sg-O

2

100

sn  24ad12
date  15  2014
DaY  2190
cy  5
al  15
drift  12
range  20
lel  20%  (fault)
print
tar
new  save
low  bat

Edit

Enter

TS1008

Se ns or

Analy ze r

*

%

2

UP              Down

L EL 2 0

Connections  Tester  TS1008

Summary of Contents for SGM595/A

Page 1: ...rotection that together with one of BE INAT s industrial type Control Units detects the presence of esplosive gas such as Methane LPG Hydrogen and other types of gas The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to it but also allows execution of a self diagnosis and therefore an AUTOMATIC CALIBRATION in order to always have the maxi...

Page 2: ...TATIONS The installation of the SGM595 A Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed ...

Page 3: ...ed personnel Side View 60 mm 80 mm 80 mm Rearward View Foro 6 5 mm 100 mm 100 mm 40 mm Front View CONTROLUNITS MOUNTING PROBES Max DEGREE PRE ALARMS POSITIVE OPERATING protec alarms safety range GS100M unit 1 zone Wall cabinet 1 I P 4 4 2 1 Y E S N O GS300M unit 1 zone Wall cabinet 3 I P 4 4 2 1 Y E S N O GS300 Mc unit 1 zone Wall cabinet 3 I P 4 4 2 1 Y E S N O BX444 MC unit 1 zone Wall cabinet 4...

Page 4: ...ow The probe detects an anomaly FAULT 1 2 3 4 5 6 C NO C NO C NO Fault Relay Pre Allarme Relay Main Alarm Relay Optional Relay Board CARD03 Linear Output 4 20 mA 100 20 100 20 SELECTION OF THE OPERATING RANGE The Conventional Probes NOT SUITABLE IN ATEX ZONE LEAVE THE FACTORY WITH A DEFAULT OPERATING RANGE VALUE SET AT 20 OF THE LEL To select the operation range to 100 LEL you need to move the jum...

Page 5: ...irectly WARNING These measurement should be performed in clean air Moreover this test must be performed only with the probe connected to a control unit or with a 220 Ohm resistance installed between terminal 2 and terminal 3 Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC Voltmeter Power Supply 12 24 V Troubleshooting before calling a technician Display legend Displays the type of probe or device Dis...

Page 6: ... controlled boiler burner industrial kitchens etc but on the opposite side 2 The probes must not be affected by fumes vapors and by sources of moving air which could distort the detection 3 The probes must not be installed near sources of heat fans or vacuum cleaners NOTE Recall that the GAS detection sensors placed inside the probe are perishable components whose average duration is variable 5 ye...

Page 7: ...e of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid s...

Page 8: ...es points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natur...

Reviews: