Page  2

Power  Supply    ......................................................................................................  12÷24VDC    ±  10%
Power  demand....................................................  90  mA  in  operating,  110  mA  in  alarm  Max  @  13,8  VDC
LEDS  diode  signals  ...........................  GREEN  light  normal  operation,  YELLOW  light  fault,  RED  light  alarm
Slot  exspansion  board relay;  CARD-03 ..................    Fault  , Prealarm,  Allarm. Relay  contacts 1A  30 VDC   SELV

Sensor    ...............................................................................................................................  Cartalityc
Sensitive  element  working  range    ....................................................................................  To  100%  of  LEL
Analog output signal  ...................................................................................... 4÷20 mA standard tolerance
Selection of the operating Range ................................................................ from 20% of LEL to 100% of LEL
Detector  accuracy  .....................................................................................................................  1%  FS
Long  term shift in clean air   ...................................................................................................  < 3% of LEL
Auto  zero  procedure    ............................................................................  Included  in  the  software algorithms
Response  Time    ............................................................................................................................  <10”
Warm-up  time  ...................................................................................................................  1,30  minutes

Functioning  humidity    ........................................................................................  0-90%  non  condensed
Functioning  temperature    ............................................................................................  -10°C  to  +50°C
Control units usable ............. BX444-Mc, BX449F, GS100M, BX180, BX280,  BX150, GS300-Mc, BX316xp, BX308xp
Max.  distance  between  probe  and  unit    ..........................................................................................  100  m
Cable  diameter  for  connecting  probe    ..............................................................................................  1  mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Probe’s  body  material    .............................................................................................................  Aluminium
External  degree  of  protection    ........................................................................................................  IP66
Size    .................................................................................................................................  100x100x60

CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper,
and as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible
damages caused to people, animals or objects.

TERMS and EXPECTATIONS:
The installation of the SGM595/A  Sensor, its ordinary and extraordinary maintenance, every
six months, and its out of service removal at the end of the functional life guaranteed by the
manufacturer, must be carried out by authorized or specialized personnel.

Do not allow it to become wet.

The control unit can be seriously damaged as it is not waterproof either when immersed in
water or exposed to high levels of humidity.

Do not drop it.

Heavy knocks or falls during transportation or installation can damage the appliance.

Avoid  abrupt  temperature  fluctuations.

Sudden  temperature  variations  can  cause  condensation  and  the  control  unit  could  work  poorly.

Cleaning

Never  clean  the  device  with  chemical  products.  If  necessary,  wash  with  a  moist  cloth.

Precautions

Technical    Specifications

WARNING!
The CATALITIC sensor has a life span of 5 to 6 years in clean air.
The working temperature of the probe recommended is from -10 ° C to + 50 ° C.
Every puffy snapshot of gas over 100% of L.I.E. Takes months off the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing aerosol.
Important:
The test of operation and eventually offset cancellation must be performed at least once a year,  by a  qualified
technician.

Technical Features  SGM595/A

Code

 

             Type  of Gas

Sen s o r

                Working  range                      Temperature

SGM595/Amet

Meth an e

Catalytic

LEL  0-100%

-10+50°C

SGM595/Agpl

LPG

Catalytic

LEL  0-100%

-10+50°C

SGM595/Aidr

H ydro gen

Catalytic

LEL  0-100%

-10+50°C

SGM595/Aace

A cetylen e

Catalytic

LEL  0-100%

-10+50°C

SGM595/Avbe

Gasoline  vapours

Catalytic

LEL  0-100%

-10+50°C

SGM595/Aalc

A lco ho l

Catalytic

LEL  0-100%

-10+50°C

Summary of Contents for SGM595/A

Page 1: ...rotection that together with one of BE INAT s industrial type Control Units detects the presence of esplosive gas such as Methane LPG Hydrogen and other types of gas The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to it but also allows execution of a self diagnosis and therefore an AUTOMATIC CALIBRATION in order to always have the maxi...

Page 2: ...TATIONS The installation of the SGM595 A Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed ...

Page 3: ...ed personnel Side View 60 mm 80 mm 80 mm Rearward View Foro 6 5 mm 100 mm 100 mm 40 mm Front View CONTROLUNITS MOUNTING PROBES Max DEGREE PRE ALARMS POSITIVE OPERATING protec alarms safety range GS100M unit 1 zone Wall cabinet 1 I P 4 4 2 1 Y E S N O GS300M unit 1 zone Wall cabinet 3 I P 4 4 2 1 Y E S N O GS300 Mc unit 1 zone Wall cabinet 3 I P 4 4 2 1 Y E S N O BX444 MC unit 1 zone Wall cabinet 4...

Page 4: ...ow The probe detects an anomaly FAULT 1 2 3 4 5 6 C NO C NO C NO Fault Relay Pre Allarme Relay Main Alarm Relay Optional Relay Board CARD03 Linear Output 4 20 mA 100 20 100 20 SELECTION OF THE OPERATING RANGE The Conventional Probes NOT SUITABLE IN ATEX ZONE LEAVE THE FACTORY WITH A DEFAULT OPERATING RANGE VALUE SET AT 20 OF THE LEL To select the operation range to 100 LEL you need to move the jum...

Page 5: ...irectly WARNING These measurement should be performed in clean air Moreover this test must be performed only with the probe connected to a control unit or with a 220 Ohm resistance installed between terminal 2 and terminal 3 Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC Voltmeter Power Supply 12 24 V Troubleshooting before calling a technician Display legend Displays the type of probe or device Dis...

Page 6: ... controlled boiler burner industrial kitchens etc but on the opposite side 2 The probes must not be affected by fumes vapors and by sources of moving air which could distort the detection 3 The probes must not be installed near sources of heat fans or vacuum cleaners NOTE Recall that the GAS detection sensors placed inside the probe are perishable components whose average duration is variable 5 ye...

Page 7: ...e of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid s...

Page 8: ...es points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natur...

Reviews: