Page 4
5) Fault
1) Power
2) Battery
3)
OL
Probes
4) OL Battery
6)
P re
Alarm
7) Main Alarm
8) Exit Alarm
9) Siren Status
12) TEST 13) RESET
14)
10) RX 11) TX
ENTER
1) Power. Green led, electric network. This LED lights up when the power supply is applied.
2) Battery. Green Led, this LED lights up with the power led when the device is powered by battery. When
the green LED flashes, the battery is low.
3) OVER LOAD SENSORS. Yellow led. This LED indicates a short circuit or a high current absorption to the
sensors. Check the sensors and the connecting cables.
4) OVER LOAD BATTERY. Yellow led. This LED lights when the battery is connected incorrectly or has an
abnormal power consumption. Proceed to the battery and connecting cables.
5) Fault. When this yellow LED lights up and flashes it means that one of the connected sensors is fault or:
the connection cables are interrupted, or there has been a connection error.
When this Led is switched on, the equipment is no longer able to detect and enables all alarm relays.
To reactivate the operation, repair or clear the sensor, using the setup program and press the RESET button.
6) Pre-Alarm. When the red light comes on, one of the connected senors detects the gas dispersed in the
environment and reached a concentration varying from 8 to 16% of the LEL and closes the contact of the relay
1st THRESHOLD.
7) Main Alarm. When turns on the red alarm LED, one of the sensors has detected a gas concentration of 20%
of the LEL. and closes the contact of the GENERAL ALARM relay.
8) Exit Alarm. When the red light of the manual alarm light turns on, a manual alarm button is pressed
9) Siren Status. When the red LED is lit, the external siren has been switched off.
10) TRANSMISSION RX Data reception. yellow Led flashing of Data reception “BUS RX”
11) TRANSMISSION TX Data transmission. Yellow Led flashing of data transmission “BUS TX”
12) TEST button. Pressing this button you get the simulation of a gas leak.
13) RESET button. Press the button to reset all memories of the events detected.
14) USB port for printer. Prints current status of the unit and sensors or the data from Datalogger.
TOTAL RESET button. Use this button only in case of extreme necessity. Return the BXI32 to the factory data
Screen displayed when turning on the BXI32
This screen remains on for 90 seconds
Beinat S/N AD012G
25 Set/17 10:10
= = BXI32 v. 1.0 = =
CountDown : 03
BXI32 Components and commands