background image

Page15

1)  When  switched  on,  the  display  of  the  BXI32  lights  up  as  BEINAT  Srl.  After  10  seconds  the  product
information  will  be  displayed  such  as:
Bein at
Serial  number  with  6  digits
Date  and  time
Product  code  example  BXI32  and  software  version
CountDown; the countdown has a duration of 90 seconds, 
  at  the  end  of  it,  the  unit  will be  ready  for  use
Meanwhile,  all  LEDs  will  light  up  cyclically,  by  doing  so  a  Functionning  test.
2)  At  the  end  of  the  countdown  the  display  stands  so  regular  operation  represented  by  the  display  designed.

MANUAL  TEST
3)
  Press  the  TEST  button  to  get  the  simulation  of  a  gas  leak,  and  the  control  panel  performs  the  following
operations  for  all  connected  sensors:
a)Lights  up  the  Preallarme  LED  ,  by  switching  the  1st  threshold  relay.  The  buzzer  emits  a  sound  to  slow
frequency.
b)Then  turns  on  the  general  alarm  LED.  In  addition  to  switching  the  pre-alarm  relay,  also  switches  the
general  alarm  relay,  the  MAIN  ALARM  LED  starts  blinking;  the  buzzer  emits  a  sound  at  a  higher  frequency.
Releasing  the  TEST  button  you  see  the  opposite  effect:  only  the  MAIN  ALARM  relay  LED  will  be  blinking.
The  general  alarm  will  persist  until  the  RESET  button  is  pressed  resetting  the  alarm  memory.

TEST  WITH  GAS
To  perform  GAS  testing,  a  pre-calibrated  gas  bottle  must  be  used  with  the  type  of  gas  for  which  the  system
has  been  built.  Carefully  read  the  sensor  user  guide  and  run  the  sensor  test.

FA ULT
There  are  two  Fault  types:
a)  Fault  Serial  Connection:  appears  on  the  display  ERR.  COM.  (communication  error).  To  test  just
disconnect  a  connection  wire.
2)  Sensor  fault:  To  simulate  this  test,  disconnect  the  sensor,  FAULT  appears  on  the  display.

-  If  the  unit  does  not  start
If  the control  unit is  supplied with  Box
,  check  that  the  voltage  110/230  VAC  is  present  at  the  ends  of  the
connection  terminals.
-  If  the  control  unit  is  supplied  without  Box,  check  that  the  voltage  15  VDC,  is  present  at  the  ends  of  the
connection  terminals.

-  If  the  Fault  yellow  LED  lights  up.
a)  
First  check  the  fault  source:  from  the  serial  network  or  from  the  sensor.
Communication  Error
If  the  fault  comes  from  the  serial  communication  check:  
that  the  cables  have  been  correctly  connected
and that the cables  are of the type recommended by  the manufacturer;  Make sure you have inserted the jumper
end  line
FA ULT
Check  that  the  sensor  wires  are  connected  as  in  the  drawing,  not  to  have  pinched  the  insulating  sheath.
Check  that  the  voltage  at  terminals  1-2  is  greater  than  11  VDC

-  If  the  Yellow  Overload  Probes  LED  lights  up
Che ck :
That  the  power  polarity  is  not  reversed,  that  there  is  no  short  circuit,  that  the  sensors  have  not  been  damaged
during  installation,  that  it  does  not  absorb  an  excessive  current.
-  If  the  Yellow  Over  Load  Battery  LED  lights  up
That  the  power  polarity  is  not  reversed,  that  there  is  no  short  circuit,  that  the  polarity  has  not  been  reversed
or  the  battery  is  not  damaged.
If  the  control  unit  is  repeatedly  in  alarm.
Check  that  there  is  no  gas  leak.
Check  that  the  FAULT  Led  does  not  light  up  with  the  alarm  signal,  in  this  case  control  the  sensors.
If  the  control  unit  is  repeatdly  in  alarm  and  does  not  close  the  equipment  connected  to  it.
Check  that  the  connections  are  correct  and  that  the  jumper  that  carries  voltage  to  the  common  relay  has  been
made.
N.B.  All  relays  are  voltage  free.  Check  the  connection  drawing.
If  the  BXI32  is  connected  to  a  12VDC  Solenoid  Valve  and  does  not  work  well.
The  BXI32  can  be  connected  directly  to  12  VDC Solenoid  valves,  Sirens  with  a  maximum absorption  of  400 mA.

In  the  event  of  further  problems,  you  should  contact  a  authorised  technician  directly  or  the  BEINAT  S.r.l.  dealer.

SN  AD012G                16/Aug/13

Methane                              10:10
sensor  32                Exp. 020%

00,0%  LEL

Turning and testing

Before calling a technician check...

Summary of Contents for BXI32

Page 1: ...sary Self diagnosis of the whole system with detections Alarms faults transmissions malfunctions etc Data Logger storage 50 episodes Ordinary maintenance program Alarms Source Automatic reading of the gas type of each sensor Adjustable alarm level for each sensor Automatic operating range from 20 to 100 LEL Efficiency of the connected sensors Positive Security Function Possibility of inserting Rel...

Page 2: ...by entering the Password All operation and alarm LEDs read page 3 to find out their functions LED that displays the charge status of Buffer battery Main Power Supply 15 VDC 10 Power demand from 1 2W min to a max of 3W Max 15 DC Secondary power supply via battery Max 2 2 Ah not supplied 12 7 V 10 Battery Charger Max 2 2 Ah controlled Relay Contact Range 10A 250V resistive ALARMS Pre Alarm adjustabl...

Page 3: ... with a moist cloth Precautions MAINTENANCE The user periodically every 6 months must perform a check of the operation of the control unit by spraying a suitable test gas at the base of the sensors connected until the alarm condition is reached At least once a year make a more accurate check by a specialist technician Disabling the detector must be carried out by qualified personnel Suitable senso...

Page 4: ... the RESET button 6 Pre Alarm When the red light comes on one of the connected senors detects the gas dispersed in the environment and reached a concentration varying from 8 to 16 of the LEL and closes the contact of the relay 1st THRESHOLD 7 Main Alarm When turns on the red alarm LED one of the sensors has detected a gas concentration of 20 of the LEL and closes the contact of the GENERAL ALARM r...

Page 5: ...ogram provides to enter a password La Password di fabbrica è 1 2 3 4 The Password can be changed by accessing to Advanced Functions program under General Functions Move with the left button above the required number and press ENTER every asterisk will turn on every number until all four asterisks are switched on If the PassWord is correct it reads Accepted Password If you enter the wrong code you ...

Page 6: ...thing stationary for three minutes the saving is automatic Down UP Left Right ENTER Detection sensors Input settings Sensors Expansion Card Selection To the controller you can associate the following connections 1 connections up to 32 sensors 2 connections up to 31 sensors and a CARD TX4R 3 connections up to 30 sensors and two CARD TX4R To do this you need to acquire the both the sensors that the ...

Page 7: ...rst 10 20 scale can be set as desired keeping in mind that the intervention threshold cannot be lower than the pre alarm To be set the second scale needs a set the probe concerned to detect 100 b a password is required to proceed Sensor 01 491940 E T Alarm 20 LEL 20 100 READING PERCENTAGE LEL RANGE SENSOR SET 20 RANGE SENSOR SET 100 The program provides to enter a password La Password di fabbrica ...

Page 8: ...the function you want to subject to relay 1 FOR EXAMPLE FAULT THRESHOLD ALARM Move with the DOWN button above the word sensors With the ENTER button select the sensor to be subjected to relay 1 Continue as above for both the relays and the remaining functions card TX4R 31 Relay 01 02 03 04 Func not used Sensors 1 32 preallarme allarme avaria ADDRESS RELAY NUMBER EVENT SUBJECT Down UP Left Right EN...

Page 9: ...E UP AND DOWN BUTTONS TO THE NEXT SELECTION Depending on the type of the system it is possible to choose the need to select the Positive Safety Selection Use the UP and DOWN buttons to select Positive Safety Each time you press ENTER button changes the written ON OFF ON enables the Positive Security function OFF disables the Positive Safety function Once chosen move with the UP and DOWN buttons on...

Page 10: ...isodi The control unit program provides the possibility to silence the external siren which may be annoying during the test phase or during the prolonged alarms The extern siren silencing is signaled by a red LED a Illuminated red LED siren silenced b LED off operating siren Press ENTER button to change ON OFF To move between the lines press the UP and DOWN Page 10 Down UP Left Right ENTER change ...

Page 11: ...Sensor replacement E15 S01 17 Central Communication Error E16 S01 Use the UP and DOWN buttons to select the written a Print status press ENTER The current status of the control unit and sensors b Print Datalogger press ENTER All datalogger events Page 11 STAMPA STATO ATTUALE ED EVENTI DEL DATALOGGER EXIT BEINAT BXI32 Ver 1 14 S N Example Serial 0102 Date Hour 31 MAY 17 10 00 Datalogger Event 01 06...

Page 12: ...agnosis consists in carrying out a check up of operation of the entire system in case of anomalies and if necessary resort to repair Examples of reading E01 CE00 central side communication error E01 SE15 sensor 15 communication error E01 EE31 expansion communication error 31 END To exit the program select Return arrow During the Maintenance period the writing In Maintenance 20m appears on the firs...

Page 13: ...will be totally reset and starts a new countdown of 90 seconds The control unit is now reset N B be sure of what is done because doing this all the previous settings will be lost Down UP Left Right ENTER Factory Reset Advanced Functions follow Maintenance 00 factory reset Indicator to return to the previous page use UP and DOWN keys and press ENTER Indicator to advance to the ALARM THRESHOLD SELEC...

Page 14: ...h a degree of IP protection depending on the area to be monitored Kitchens Boiler rooms Laboratory etc choosing one of the Beinat s sensors ranging from IP30 to ATEX vedi pagina 3 Sensors installation and positioning 30 cm Light Gas 30 cm Heavy Gas Average Height Volatile Gas INSTALLATION OF GAS SENSORS It is important to remember that remote sensors should be installed bearing in mind that 1 The ...

Page 15: ... the ends of the connection terminals If the control unit is supplied without Box check that the voltage 15 VDC is present at the ends of the connection terminals If the Fault yellow LED lights up a First check the fault source from the serial network or from the sensor Communication Error If the fault comes from the serial communication check that the cables have been correctly connected and that...

Page 16: ...ternal siren BEINAT S N AD012G 31 07 17 10 10 BXI32 ver 1 4 CountDown 03 S2 S1 S30 S29 C31 C32 C B A C B A RS 485 Max 1000 meters N B Close jumper end of line of the last device Codice ASI012 Power supply for 8 sensors 110 230 VAC 15 VDC Note Each sensor absorbs 200 mA PAM NC Reset button Ext Alarm 12 V Powersupply 15 VDC Powersupply 110 230 VAC Block diagram electrical connections ...

Page 17: ... switches that each device possesses until a maximum of 32 addresses Example to select an address Turn the Switch of tenths until you find the desired tenth For example 1 Turn the Switch of units until you find the desired unit For example 6 In this way you set the address 16 REMEMBER TO INSERT THE END LINE CLOSURE AT THE LAST SENSOR OR CARD Selecting line end Open Close ON 3 2 1 C B A 1 2 3 4 5 6...

Page 18: ...until you find the desired tenth For example 0 Turn the Switch of units until you find the desired unit For example 6 In this way you will set the address 6 Remember to insert the end of line closure to the last sensor or card Yellow LEDs transmission Power supply 15 VDC Transmission 3 C 2 B 1 A Connection and Addressing of an additional Relay Card CARD TX4R follows Electrical Connections WARNING ...

Page 19: ...pplies In the RS485 network the masses of the devices must be connected together In the case of devices with power supply connected to earth for example PC the earth and ground connection together can generate problems 1 The total length of the RS485 network must not exceed 1000 meters 2 The minimum distance between two devices must not be less than 1 meter 3 The branch line from the main network ...

Page 20: ...s of a solenoid valve Normally Closed with Positive Safety Connecting a Solenoid valve with sirens to 12 VDC via a power switcing The power supply should be adequate to the consumption of the components C NC NO C NC NO C NC NO C NC NO 1 2 3 4 5 6 7 8 9 Solenoid valve Prealarm Fault Siren ext NA NC Switching power supply 230 VAC Ph N 12 VDc Electrical connections Connections of a solenoid valve Nor...

Page 21: ... 0 2 8 0 BEINAT S N AD012G 21 10 15 10 10 BXI ver 1 4 Count Down 90 BXI32 90 mm 45 mm 37 mm 90 mm 45 mm 159 mm Measures and dimensions of the unit in rail DIN Omega 9 modules Measurements and dimensions of the control unit in box IP65 ...

Page 22: ...istributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid station and inform the operators that you could have been poisoned by Carbon Monoxide or by an excess or deficiency of oxygen NOT...

Page 23: ...Page 23 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Sensors n Code Address Location Type of gas Reminder table of the addressed sensors configuration ...

Page 24: ...points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natural ...

Reviews: