Page 3
CHECK the integrity of the control unit after removing it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and as a result of
which BEINAT S.r.l. therefore disclaims any responsibility for possible damages caused to people, animals
or objects.
IMPORTANT: The operating test should not be performed with the gas tap because this don't provide enough
gas concentration to trigger the general alarm.
TERMS and EXPECTATIONS: The installation of the art. BXI32, its ordinary maintenance once a year
Including the sensors operation and its disposal at the end of the functional life guaranteed by the manufacturer,
must be carried out by authorized and/or specialized personnel
To use your control unit for a long time and with satisfaction, use it with the following precautions:
Keep dry.
The control unit is not waterproof if it is immersed in water or exposed to high humidity levels can result in
serious damage.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the sensor could work poorly.
Beyond the temperature + 60 ° C about, the display becomes black, in this case you must cool it to make it
visible
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Precautions
MAINTENANCE
The user periodically (every 6 months) must perform a check of the operation of the
control unit by spraying a suitable test gas at the base of the sensors connected until the
alarm condition is reached.
• At least once a year make a more accurate check by a specialist technician.
• Disabling the detector must be carried out by qualified personnel.
Suitable sensors by zone and type of gas
Protect. ZONE Detected operating Automatic
Probe
SENSOR DEGREE
Suitable for
GAS
RANGE OUTPUT PRECIS. CALIBRATION
SGM595
Catal yti c
I P 5 5
Tertiary seepricelist
0÷100% LIE Digital
±5 %
S I
SGM595/A
Catal yti c
I P 6 5
Zone 2
seepri cel i st
0÷100% LIE Digital
±5 %
S I
SG895 Catalytic
ATEX
Zone 1
seepri cel i st
0÷100% LIE Digital
±5 %
S I
SG580 Catalytic
I P 6 5
Zone 2
seepri cel i st
0÷100% LIE Digital
±5 %
S I
SGF101
Catal yti c
I P 6 4
Zone 2
Methane
0÷100% LIE Digital
±5 %
S I
SGF103
Catal yti c
I P 6 4
Zone 2
L P G
0÷100% LIE Digital
±5 %
S I
SGF111
Electrochimical IP64
Zone 2 CO
0÷300% ppm Digital
±5 %
S I
SGF113
Catal yti c
I P 6 4
Tertiary
Hydrogen
0÷100% LIE Digital
±5 %
S I
CARD-TX4R, max. 2
Expansion Card 4 Digital Relay
Legend
Domestic Locations: Households. Boiler rooms max 38000 kW-h
Tertiary locations: Big boiler rooms, workshops, warehouses of materials, industrial kitchens, big building complexes,
f ac t or ies .
Zone 2- Mixed IP65 ATEX: Locations with great probality of gas escape, locations high risk, locations for which compliance
regulations are in force
Zone 1- Hazard ATEX: Locations high risk, locations for which compliance regulations are in force, gas bottles warehouses,
solenoid valve control or mixed ramps
Oxygen alarm levels
1° Pre-Alarm
Main alarm
Legend:
< Oxygen deficienty
> Excess Oxygen
<
19.9 %
>
21.9 %
<
18.5 %
>
23.5 %