4
1.4
SPECIFICATIONS
The specifications listed below apply to standard models. Model options and engineering specials will
vary as stated in appropriate addendums. Refer to name tag located on equipment for proper
identification.
INPUT POWER
Voltage:
see chart on preceding pages
Frequency:
47-63 Hz.
OUTPUT POWER
Voltage:
0-135 Vac Line - Neutral , 3
N
* ( standard )
Frequency:
45-500 Hz ( 45 to 1KHz for E option units )
Maximum Power:
10000 VA
Maximum Current:
25 amperes per phase ( standard models )
Current Crest
Factor:
3:1.
Power Factor:
100% of rated output into any power factor load.
Distortion:
1.5% maximum THD (measured at full load, 100 Vac, 50 Hz).
Load Regulation:
±0.7% from no load to full load. ( 250msec typical )
Line Regulation:
±0.1% for ±10% of line change.
Efficiency:
85-90% ( with 3 phase input )
METERING
L.E.D display of Voltage : resolution 1.0V, ac/- 2% @ F.S.
L.E.D display of Current : resolution 0.1A, ac/- 2% @ F.S.
L.E.D display of Frequency : resolution 1Hz, ac/- 2Hz
MECHANICAL
Dimensions:
2 Standard EIA 19 in. rack wide chassis, 1
5.
75in. Total height , 22 in.
deep .( 3 phase in with no options.) See additional info for single
phase inputs.
Weight:
2
50 lbs. ( 3 phase inputs without options )
Operating
Temperature:
0°C to 55°C (32°F to 131°F).
* Voltage may vary. See option list, page 1.
Summary of Contents for BL10000 Series
Page 9: ...3 THIS PAGE BLANK FOR ADDENDUMS ALL MANUAL ADDENDUMS WILL FOLLOW THIS PAGE ...
Page 17: ...11 Figure 3 1 BL10000 AC Source Control Chassis Front and Rear Panel Views ...
Page 49: ...6 1 SECTION 6 DRAWINGS ...
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......