Mounting and wiring
EL922x
50
Version: 1.0
The EL9227-xxxx has illuminated push-buttons!
The illuminated push-buttons allow the overcurrent protection terminal to be operated, e.g. switch-
ing on and off and resetting the respective output. They are also used for programming and query-
ing the nominal current. There are 3 modes: operation mode, programming mode and query mode.
There is a common programming mode in which the two outputs can be set simultaneously, as they
are interdependent for the terminal with sum current limitation.
Overview of the 3 operation modes:
Operation mode
The operation mode is active as soon as the overcurrent protection terminal is supplied with supply voltage,
the initialization has been successfully completed and no other mode is active. This is effectively the normal
mode of operation.
Programming mode
The programming mode is available for the adjustable overcurrent protection terminals. To enter this mode,
press and hold one of the two buttons in operation mode for > 3 seconds. In programming mode, both
outputs can be set simultaneously.
Query mode
The query mode exists for the fixed overcurrent protection terminals, which are not adjustable. If
programming is disabled for the adjustable overcurrent protection terminals, only the query mode is
available. No changes can be made in query mode, i.e. it is only intended for querying the nominal current
value. To enter this mode, press and hold one of the two buttons in operation mode for > 3 seconds.
For operation in the respective modes, please refer to the table LED buttons Operation / Programming.
Button LED Operation / Programming
LED
State
Meaning
Operation in operation mode
Button LED 1
Press briefly
Switching output 1 on and off or resetting it
Long press (>3s)
Activating the programming or query mode
Button LED 2
Press briefly
Switching output 2 on and off or resetting it
Long press (>3s)
Activating the programming or query mode
Operation in programming mode
Button LED 1
Press briefly
Set nominal current value of output 1, press 1x = 1 A, press 2x = 2 A etc. up to
press 10x = 10 A,
press more than 11x= OFF
For variants up to 4 A,
press more than 5x = OFF
applies
Long press (>3s)
Saving the nominal current value and leaving the programming mode
Button LED 2
Press briefly
Set nominal current value of output 2, press 1x = 1 A, press 2x = 2 A etc. up to
press 10x = 10 A,
press more than 11x= OFF
For variants up to 4 A,
press more than 5x = OFF
applies
Long press (>3s)
Saving the nominal current value and leaving the programming mode
Press button LEDs 1 and 2 simultaneously for > 5 s
Resetting to factory settings
No operation for 45 seconds
After 45 seconds, the programming mode is automatically exited without saving
the settings.
Operation in query mode
Button LED 1
Press briefly
No function
Long press (>3s)
Exiting the query mode
Button LED 2
Press briefly
No function
Long press (>3s)
Exiting the query mode
No operation for 45 seconds
After 45 seconds, the settings query mode is automatically exited again
Sample programming