Commissioning
EL922x
123
Version: 1.0
7.6.2
EL9222-xxxx
7.6.2.1
Restore object
Index 1011 Restore default parameters
Index
(hex)
Name
Meaning
Data type
Flags Default
1011:0
Restore default parame-
ters
Restore default parameters
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to "
0x64616F6C"
in the set value dia-
log, all backup objects are reset to their delivery state.
UINT32
RW
0x00000000 (0
dec
)
7.6.2.2
Configuration data
Index 80n0 Settings (for n = 0, Ch.1; n=1, Ch. 2)
Index (hex) Name
Meaning
Data type
Flags
Default
80n0:0
Settings
Max. Subindex
UINT8
RO
0x19 (25
dec
)
80n0:11
Nominal current
Nominal current (set fuse value), I
N
UINT8
RW
(0x80nF:17)
80n0:19
Switch Programming
Control
LED button programming option: Indicated whether
the nominal current of programmable terminals can
be programmed via the LED button.
Disable
: Locked and not allowed. Only one query of
the nominal current is possible!
Enable
: Programming possible
UINT8
RW
---
Index 80n0 DIG Safe State Active Ch.n
(n=2 for Ch.1; n=3 for Ch.2
Index
(hex)
Name
Meaning
Data type
Flags Default value
80n0:0
DIG Safe State
Active
Maximum subindex
UINT8
RO
0x01 (1
dec
)
80n0:01
Active
Enabling of the output state defined in
index 0x80n1:01 in case of a bus error
0: output retains its current state.
1: output is switched to the state defined in
index 0x80n1.
BOOLEAN RW
0x01 (1
dec
)
Index 80n1 DIG Safe State Value Ch.n
(n=2 for Ch.1; n=3 for Ch.2
Index
(hex)
Name
Meaning
Data type
Flags Default value
80n1:0
DIG Safe State
Value
Maximum subindex
UINT8
RO
0x01 (1
dec
)
80n1:01
Value
Defines the state of the output in case of a
bus error:
0: output off
1: output on
BOOLEAN RW
0x00 (0
dec
)