Commissioning
EL72x1-901x
152
Version: 1.9
• With
TP1 Continuous
you can decide whether the position is to be saved only at the first event (
TP1
Continuous
= false) or whether this should take place at every event (
TP1 Continuous
= true).
For example, if
TP1 Continous
and
TP1 Enablepos edge
are set, the position is saved on each positive
edge at input 1 of the terminal.
If
TP1 Enable neg edge
is set and
TP1 Continuous
is not set, the position will only be saved on the first
negative edge at input 1 of the terminal. If you wish to repeat this procedure, you must first deactivate
TP1 Enable
and then activate it again. Then the position is saved again on the first negative edge.
•
TP1 Trigger mode
has no function in the case of the EL72x1-xxxx.
• The saved position of the positive edge can be read in the inputs of the process data under
TP1 Pos
position
, that of the negative edge under
TP1 Neg position
.
• The variables under
Touch probe status
are for the diagnosis.
• The Touch Probe inputs must be addressed with a 1-wire +24 V signal.
5.4
Operation modes
5.4.1
Overview
Operating modes CST, CSTCA, CSV and CSP are supported. The operating mode is set in the CoE list in
index
Modes of operation (MDP) or index
Modes of operation (DS402). In
the respective process data the user can additionally select the respective
Predefined PDO Assignment
. All
required variables are then in the process data.
152] - cyclic synchronous velocity (velocity control)
In CSV mode the EL72x1-xxxx operates with the cyclic velocity interface. A defined velocity can be set via
the
Target velocity
variable.
156] - cyclic synchronous torque (torque control)
In CST mode the EL72x1-xxxx operates in the cyclic torque interface. A defined torque can be set via the
Target torque
variable.
159] - cyclic synchronous torque with commutation angle (torque control with commutation
angle)
This operating mode is also intended for use with the cyclic torque interface. In addition the user can specify
the commutation angle. The variable
Commutation angle
can be used to set an angle which is to be
maintained with a defined torque set in variable
Target torque
.
163] - cyclic synchronous position (position control)
In the CSP operating mode the EL72x1-xxxx operates in the cyclic position interface. A defined position can
be set via the
Target position
variable.
For further information on the three operating modes described above please refer to section
“Commissioning without NC”.
5.4.2
CSV
CSV - cyclic synchronous velocity (velocity control)
In CSV mode the EL72x1-xxxx operates with the cyclic velocity interface. A defined velocity can be set via
the
Target velocity
variable.
Summary of Contents for EL72 1-901 Series
Page 2: ......
Page 6: ...Table of contents EL72x1 901x 6 Version 1 9...
Page 20: ...Product overview EL72x1 901x 20 Version 1 9 2 3 Technical data...
Page 49: ...Installation EL72x1 901x 49 Version 1 9 Fig 36 Shield busbar Fig 37 Shield busbar clamp...
Page 141: ...Commissioning EL72x1 901x 141 Version 1 9 Fig 176 DS402 State Machine...
Page 150: ...Commissioning EL72x1 901x 150 Version 1 9 Fig 184 Touch Probe inputs...
Page 172: ...Commissioning EL72x1 901x 172 Version 1 9 Fig 207 Process Data tab SM2 EL72x1 0010 default...
Page 256: ...Appendix EL72x1 901x 256 Version 1 9 9 5 Certificates Fig 233 EL72x1 9014_Certificate...