Parameterization and commissioning
EL6731
119
Version: 2.8
Offset
Description
0 -125
BusStatus List, one byte per station address 0-125 which contains the station status (see
BoxState for PROFIBUS boxes and for non-selected stations: 0x80 - not present, 0x81 -
slave, 0x82 - master not ready for token ring, 0x83 - master ready for token ring, 0x84 -
master in token ring).
126 - 127
reserved
128 - 135
State of the EL6731
130 - 131
detected bus errors
136 - 137
Send error counter for all sent telegrams.
138 - 139
Receive error counter for all received telegrams.
140 - 255
reserved for extensions
256 - 257
Sync Failed Counter (see
tab)
258 - 259
Cycle Start Error Counter, counts up one when the PROFIBUS cycle is restarted before the
old cycle is complete (intercepted by the TwinCAT-IO driver, only possible with customized
drivers).
260 - 261
Time Control Failed Counter (see
262 - 263
reserved for extensions
264 - 265
Minimum reload value of real time timer.
266 - 267
Maximum reload value of the real-time timer (max. jitter, see
tab, = max.
reload value - min. reload value)
268 - 269
270 - 271
PLL Underflow Counter (see
tab)
296 - 297
Output-Failed-Counter
298 - 299
Input-Failed-Counter
300 - 301
actual Cycle-Time (µs)
302 – 303
min. Cycle-Time (µs)
304 - 305
max. Cycle-Time (µs)
306 - 307
CycleWithNoDxch-Counter
308 - 309
CycleWithRepeat-Counter
310- 311
max. Repeat/Cycle
Further information on the diagnostic data
Further information on the diagnostic data can be found in the chapter
5.1.8.4
Slave diagnosis
DP-State
Each DP slave has a status variable that indicates the current state of that DP slave. This status is
maintained in real time, so that it is always adapted to the current DP slave data, and can be linked to a PLC
variable (->
of the slave):
Fig. 121: Input DpState in the TwinCAT tree