CLTI- & CLXI-1MC4

 

Terminal Block & Module Locations (Single-wide Enclosure) 

Functional Summary 

MODULE

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

 

The Crestron

 1-Feed, 4-Motor Terminal Block and 

Module (CLTI-1MC4 and CLXI-1MC4, respectively), are 
considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLTI-1MC4 prior to installation of the 
CLXI-1MC4, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate the circuit feed (HOT and NEUTRAL) and 
distribute the controlled circuits (LOAD) to the motors. 
The module connects to the terminal block and performs 
control of four bi-directional motors. The maximum load 
is 8 amps (1 HP) for any controlled circuit, limited to 13 
amps total per module. The unit requires 230VAC 50 Hz, 
1 phase input voltage. An oversize heat sink dissipates 
heat efficiently. There are LEDs on the module to indicate 
communication to a Cresnet

 network, input power to the 

module, and output power to the load. 

Installation 

Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

Terminal Block & Module Locations (Double-wide Enclosure) 

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
0

°

C to 40

°

C (32

°

F to 104

°

F). The relative humidity 

must be 0% to 90% (non-condensing).  

GROUNDING TERMINAL BLOCKS

MODULE

TERMINAL BLOCK

(LEFT)

TERMINAL BLOCK

(RIGHT)

 

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6409

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2013811)

 

Tel: 888.CRESTRON

 

11.05

 

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Summary of Contents for CLTI-1MC4

Page 1: ...estron Automation Enclosure by a licensed electrician in accordance with all national and local codes Terminal Block Module Locations Double wide Enclosure CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a well ventilated area The ambient temperature must be 0 C to 40 C 32 F to 104 F The relative humidity must be 0 to 90 non condensing GROUNDING TERMINAL BLOCKS MO...

Page 2: ...jumper NOTE Use copper conductors only rated 75 C 2 With the circuit breaker turned off connect the circuit feed HOT and NEUTRAL and controlled circuit LOAD wires to the terminal block per the markings provided on the wiring label as shown in the diagrams on this page Terminal blocks accept one 2 5 6 0 mm2 wire Wires should be stripped to 12 mm Tighten terminal blocks to 1 Nm Do not over tighten W...

Page 3: ...and is the same color as the terminal to which it should be connected Wires are pre stripped to 12 mm Tighten to 1 Nm Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE ...

Page 4: ...erials and workmanship under normal use for a period of three 3 years from the date of purchase from CRESTRON with the following exceptions disk drives and any other moving or rotating mechanical parts pan tilt heads and power supplies are covered for a period of one 1 year touchscreen display and overlay components are covered for 90 days batteries and incandescent lamps are not covered This warr...

Reviews: