Product overview
EL3773
15
Version: 2.5
•
3.2
Technical data
Note
RMS value (rms) specifications
All AC value specifications in this documentation such as RMS specifications (rms) refer to
a 50/60 Hz 3-phase mains network with a sinusoidal waveform (crest factor 1.414).
Technical data
EL3773
Number of inputs
3 x current, 3 x voltage
Oversampling factor
n = 1…100 selectable
Distributed Clocks
yes
Accuracy of Distributed Clocks
<< 1 µs
Input filter limit frequency
adjustable, 200 ... 15,000 Hz
Conversion time
min. 100 µs, all channels measured simultaneously
Rated mains voltage
230 V
rms
(UL
X
-N) or 400 V
rms
(UL
X
-UL
Y
)
Voltage measuring range (nominal range)
DC: ±410 V
AC accordingly: 500 V
rms
AC 3~ (UL
X
-N: 288 V
rms
AC)
common reference potential N/GND*
Max. permitted overvoltage
max. ±500 V (peak value, UL
X
-N, corresponds with 353 V
rms
) *
Voltage resolution
1 digit ~ 12.5 mV (16 bit incl. sign)
Input resistance voltage circuit
typ. 1.8 MΩ
Current measuring range (nominal range)
DC: ±1.5 A
AC accordingly: 3 x 1 A
rms
*
AC recommended via measuring transformer x A AC/1 A AC
Max. permitted overcurrent
max. ±1.8 A (peak value, corresponds with 1.2 A
rms
) *
the upstream use of current/limiting current transformers is recommended
Current resolution
1 digit ~ 45.7 µA (16 bit incl. sign)
Input resistance current path
typ. 30 mΩ
Signal type
variable
Measuring error (for DC measuring)
< ±0.5 % (relative to full scale value)
Electrical isolation
2,500 V
Current consumption of power contacts
-
Current consumption via E-bus
200 mA typ.
Configuration
via TwinCAT System Manager
Weight
approx. 75 g
permissible ambient temperature range during opera-
tion
0°C ... +55°C
permissible ambient temperature range during storage -25°C ... +85°C
permissible relative humidity
95 %, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27,
see also
installation instructions for enhanced mechanical load capacity [
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE,
* operation for longer periods above the rated range can impair the function and/or lead to a shortening of
the service life
Summary of Contents for EL3773
Page 1: ...Documentation EL3773 Power Monitoring Oversampling Terminal 2 5 2018 03 13 Version Date...
Page 2: ......
Page 6: ...Table of contents EL3773 6 Version 2 5...
Page 39: ...Mounting and wiring EL3773 39 Version 2 5 Fig 29 Other installation positions...
Page 41: ...Mounting and wiring EL3773 41 Version 2 5 Fig 31 Block diagram...
Page 47: ...Commissioning EL3773 47 Version 2 5 Fig 38 Incorrect driver settings for the Ethernet port...
Page 147: ...Commissioning EL3773 147 Version 2 5 Fig 168 Confirming program start...