Product overview
EL31xx-00xx
25
Version: 5.9
2.5.2
EL315x - Technical data
Technical data
EL3151
EL3152
EL3154
analog inputs
1 (single ended)
2 (single ended)
4 (single ended)
Signal current
4 mA…20 mA
Distributed Clocks
yes
yes (from
rev.
EL315x-0000-0017 [
}
206]
)
yes
Distributed Clocks precision
<< 1 µs
Internal resistance
85 Ω type. + diode voltage
Input filter limit frequency
5 kHz
Dielectric strength
max. 30 V
Conversion time (default setting:
50 Hz filter)
approx. 40 µs
approx. 60 µs
(Fast mode: approx. 40 µs)
approx. 100 µs
Resolution
16 bit (including sign)
Measuring error (full measuring
range)
< ± 0.3% (at 0 °C ... +55 °C, relative to the full scale value)
< ± 0.5% (when the extended temperature range is used)
Supply voltage for internal elec-
tronic
via the E-bus
Current consumption via E-bus
typ. 130 mA
typ. 170 mA
typ. 130 mA
Electrical isolation
500 V (E-bus/field voltage)
Bit width of the process image
(default setting)
Inputs: 1 x 16 bit;
Status: 1 x 8 bit
Inputs: 2 x 16 bit;
Status: 2 x 8 bit
Inputs: 4 x 16 bit;
Status: 4 x 8 bit
Configuration
no address or configuration settings required
Weight
approx. 60 g
Permissible ambient temperature
range during operation
-25°C ... +60°C (extended temperature range)
Permissible ambient temperature
range during storage
-40°C ... +85°C
Permissible relative humidity
95%, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting [
}
43]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
according to EN 60068-2-6/EN 60068-2-27,
see also
Installation instructions [
}
47]
for terminals with increased mechanical load capacity
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
ATEX [
}
55]
cULus [
}
56]