Name
Designation
Index
X
ADC
Output value of the A/D converter
0x80nE:01 [
}
195]
X
F
Output value after the filter
-
B
H
Vendor calibration offset (not changeable)
0x80nF:01 [
}
195]
A
H
Vendor calibration gain (not changeable)
0x80nF:02 [
}
195]
B
A
User calibration offset (can be activated via index
0x80n0:0A [
}
194]
)
0x80n0:17 [
}
194]
A
A
User calibration gain (can be activated via index
0x80n0:0A [
}
194]
)
0x80n0:18 [
}
194]
B
S
User scaling offset (can be activated via index
0x80n0:01 [
}
194]
)
0x80n0:11 [
}
194]
A
S
User scaling gain (can be activated via index
0x80n0:01 [
}
194]
)
0x80n0:12 [
}
194]
Y
S
Process data for controller
-
Measurement result
The accuracy of the result may be reduced if the measured value is smaller than 32767 / 4 due to
one or more multiplications.
Measurement ranges
The diagrams at the bottom show the output values of the measurement ranges and the behavior if the limit
ranges are exceeded.
EL310x, EL3112-0011, EL3142-0010
Fig. 193: Measurement ranges ± 10 V, ± 10 mA and ± 20 mA (applicable as given by ‘X’ by the following
table)