Product description
EJ6910
13
Version: 1.7.0
3.4
Technical data
Product designation
EJ6910
Number of inputs
0
Number of outputs
0
Status display
4 diagnostic LEDs
Minimum/maximum cycle time
approx. 1 ms / according the project size
Error reaction time
≤ watchdog times
Watchdog time
Min. 2 ms, max. 60000 ms
Input process image
Dynamic, according to the TwinSAFE configuration in TwinCAT 3
Output process image
Dynamic, according to the TwinSAFE configuration in TwinCAT 3
Supply voltage (SELV/PELV)
24 V
DC
(–15%/+20%)
Current consumption
approx. 222 mA
Power dissipation of the terminal
typically 1 W
Dimensions (W x H x D)
12mm x 66mm x 55mm
Weight
approx. 27 g
Permissible ambient temperature (operation)
-25°C to +55°C
Permissible ambient temperature (transport/storage)
-40°C to +70°C
Permissible air humidity
5% to 95%, non-condensing
Permissible air pressure (operation/storage/transport)
750 hPa to 1100 hPa
(this corresponds to a height of approx. -690 m to 2450 m over
sea level assuming an international standard atmosphere)
Climate category according to EN 60721-3-3
3K3
(the deviation from 3K3 is possible only with optimal environmen-
tal conditions and also applies only to the technical data which
are specified differently in this documentation)
Permissible level of contamination according to EN 60664-1
level of contamination 2 (comply with the chapter
Impermissible operating conditions
TwinSAFE EJ modules must not be used under the following
conditions:
• under the influence of ionizing radiation (that exceeds the
level of the natural environmental radiation)
• in corrosive environments
• in an environment that leads to unacceptable soiling of
the Bus Terminal
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Shocks
15 g with pulse duration 11 ms in all three axes
Protection class
IP20
Permitted operating environment
control cabinet or terminal box with minimum protection class
IP54 according to IEC 60529
Permissible installation position
Installation position and minimum distances [
Approvals
CE, TÜV SÜD
Summary of Contents for EJ6910
Page 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Page 2: ......
Page 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Page 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Page 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...