![Beckhoff EJ6910 Operation Manual Download Page 99](http://html1.mh-extra.com/html/beckhoff/ej6910/ej6910_operation-manual_2719249099.webp)
Operation
EJ6910
99
Version: 1.7.0
4.16
Diagnostics
4.16.1
Diagnostic LEDs
The LEDs Diag 1 to Diag 4 display diagnostic information for the EJ6910.
Fig. 145: EJ6910 diagnostic LEDs
4.16.1.1
LED indicators
Diagnostic LEDs
LED
lit
flashing
off
Diag 1
(green)
Environment variables,
operating voltage and internal
tests are in the valid range
• If Diag 2 flashes, a logic
error code applies
-
Environment variables,
operating voltage and internal
tests are outside the valid
range
• If Diag 2 flashes, an
environment error code
applies
Diag 2
(red)
Together with Diag 3 and 4:
Global shutdown
1)
has
occurred. (see diag history of
the TwinSAFE components)
Logic or environment error
code according to Diag1 and
tables below is output
Together with Diag 3 and 4:
Global fault
1)
has occurred. (see
diag history of the TwinSAFE
components)
Diag 3
(red)
Global fault or global shutdown
on µC1
1)
-
No global fault or global
shutdown on µC1
1)
Diag 4
(red)
Global fault or global shutdown
on µC2
1)
-
No global fault or global
shutdown on µC2
1)
1. A global fault permanently disables the TwinSAFE component, so that it has to be replaced. A global
shutdown temporarily disables the TwinSAFE component. The error can be reset by switching off and
back on again.
Summary of Contents for EJ6910
Page 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Page 2: ......
Page 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Page 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Page 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...