Logic error codes of LED Diag 2 (if LED Diag 1 is lit)
Flashing
Code
Description
1
Function block error in one of the TwinSAFE groups
2
Communication error in one of the TwinSAFE groups
3
Error combination: Function block and communication
4
General error in one of the TwinSAFE groups
5
Error combination: General and function block
6
Error combination: General and communication
7
Error combination: General, function block and communication
Environment error codes of LED Diag 2 (if LED Diag 1 is off)
Flashing
Code
Description
1
Maximum supply voltage µC1 exceeded
2
Supply voltage µC1 below minimum value
3
Maximum supply voltage µC2 exceeded
4
Supply voltage µC2 below minimum value
5
Maximum internal temperature exceeded
6
Internal temperature below minimum value
7
Valid temperature difference between µC1 and µC2 exceeded
8
not used
9
not used
10
General error
4.16.1.2
Flash code display
LED
Display
Description
flashing
400 ms ON / 400 ms OFF
1 second pause between the flash codes
flickering
50 ms ON / 50 ms OFF
Summary of Contents for EJ6910
Page 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Page 2: ......
Page 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Page 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Page 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...