Operation
EJ6910
78
Version: 1.7.0
Fig. 110: User Administration - New User added
Use the
Finish
button to exit the dialog.
Access Rights
Description
Change Password
Users can change their password.
Download Safe Logic Data
The user can load the safety program onto the EL6910, EJ6910 or
EK1960.
Download Mapping Data
The user can load the mapping data for inputs, outputs, FBs etc. onto the
EL6910, EJ6910 or EK1960.
Download Safe User Data /
Replacement Values
The user can change safe user parameters on the EL6910, EJ6910 or
EK1960change and also change and load safe substitute values
Download Info Data
The user can activate and load the info data for connections and FBs on
the EL6910, EJ6910 or EK1960.
Download Project Data in
Restore Mode
The user is allowed to perform a restore. Currently not supported.
Activate / Deactivate Groups
The user can execute Customizing (enable and disable of TwinSAFE
groups) on the EL6910, EJ6910 or EK1960.
4.7
Backup/Restore
Following the exchange of an EL6910, EJ6910 or EK1960, the previous project can be loaded to the new
device using the
Backup/Restore
mechanism.
In order to be able to use this functionality, the
Backup/Restore
mechanism must be enabled in the safety
project, and the terminals must be selected, on which the current CRC of the safety project is to be stored.
For a restore operation the user can specify the minimum number of selected terminals on which the correct
CRC must be stored.
Using the checkbox
Restore User Administration
the user can specify whether the user administration should
be transferred to the new device via the restore mechanism.
Summary of Contents for EJ6910
Page 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Page 2: ......
Page 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Page 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Page 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...