![Beckhoff EJ6910 Operation Manual Download Page 103](http://html1.mh-extra.com/html/beckhoff/ej6910/ej6910_operation-manual_2719249103.webp)
Operation
EJ6910
103
Version: 1.7.0
4.16.4.1
Index FEA0hex: CTRL Diag Data
Index
Name
Meaning
Flags Default
FEA0:09 Actual Safety Control
Task Execution Time
Current processing time of the EL6910/EJ6910 when
logic state = 1 (RUN)
cycle time = 1.25 * value
(average value of 64 cycles)
RO
0
hex
FEA0:0A Min Safety Control Task
Execution Time
Minimum processing time of the EL6910/EJ6910
when logic state = 1 (RUN)
cycle time = 1.25 * value
RO
0
hex
FEA0:0B Actual Safety Control
Task Execution Time
Maximum processing time of the EL6910/EJ6910
when logic state = 1 (RUN)
cycle time = 1.25 * value
RO
0
hex
FEA0:15 Actual Safety Control
Task Execution Time
Current processing time of the EL6910/EJ6910 when
logic state <> 1
cycle time = 1.25 * value
(average value of 64 cycles)
RO
0
hex
FEA0:16 Min Safety Control Task
Execution Time
Minimum processing time of the EL6910/EJ6910
when logic state <> 1
cycle time = 1.25 * value
RO
0
hex
FEA0:17 Actual Safety Control
Task Execution Time
Maximum processing time of the EL6910/EJ6910
when logic state <> 1
cycle time = 1.25 * value
RO
0
hex
The minimum and maximum values can be reset by writing a value to CoE object 0x1C32:08.
4.17
Maintenance
Maintenance
The TwinSAFE components are maintenance-free!
Environmental conditions
WARNING
Observe the specified environmental conditions!
Please ensure that the TwinSAFE components are only stored and operated under the
specified conditions (see technical data).
If the TwinSAFE component is operated outside the permitted temperature range it will switch to
Global
Shutdown
state.
Cleaning
Protect the TwinSAFE component from unacceptable soling during operation and storage!
If the TwinSAFE component was subjected to unacceptable soiling it may no longer be operated!
WARNING
Have soiled terminals checked!
Cleaning of the TwinSAFE component by the user is not permitted!
Please send soiled terminals to the manufacturer for inspection and cleaning!
4.18
Service life
The TwinSAFE EJ modules are designed for a service life of 20 years.
Due to the high diagnostic coverage within the lifecycle no special proof tests are required.
Summary of Contents for EJ6910
Page 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Page 2: ......
Page 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Page 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Page 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...