Configuration
CU8130-0240
41
Version: 1.1
Status in-
formation
Beckhoff BAPI
v1
Beckhoff
P24Vxxxx UPS
Beckhoff 24V
UPS on the
CP903x card
CX2100-09x4
APC
Back-
UPS
Pro
280
APC
Smart-
UPS 420
Description
Firmwar-
eRev
X
X
X
X
X
X
UPS firmware version in-
formation. Empty string if
the UPS does not support
this parameter.
SerialNum-
ber
X
X
None
X
X
X
Serial number of the UPS.
Empty string if the UPS
does not support this pa-
rameter.
Bat-
teryLifePer-
cent
X
X
None
X
X
X
Remaining battery life in
percent. The value is al-
ways zero if the UPS can-
not supply this parameter.
Bat-
teryLife-
Time
X
X
None
X
X
X
Remaining battery life in
minutes. The value is al-
ways zero if the UPS can-
not supply this parameter.
eBatteryS-
tatus
BatteryOk
BatteryUn-
knownStatus
if
no battery exists;
from UPS soft-
ware version >=
2.0.0.6 and UPS
firmware >=
25.1.I
BatteryOk
BatteryUn-
knownStatus
if
no battery exists.
BatteryOk
BatteryUnknown-
Status
when no
battery is present
(applicable only for
the model with
"Smart Battery"
and not with ca-
pacitors)
BatteryOk
X
X
Battery status (type:
E_BatteryStatus).
eComm-
Status
X
X
X
X
X
X
Status of the communica-
tion with the UPS (type:
E_UpsCommStatus).
ePower-
Status
X
X
X
X
X
X
Status of external power
supply (type: E_UpsPow-
erStatus).
nPower-
FailCnt
X
X
X
X
*X
*X
Power-fail counter. The
counter is incremented if a
voltage failure is detected
by the UPS service.
dwCharge-
Flags
No Battery
(bit 7
set) from UPS
firmware
>=33.12-0 if no
battery iscon-
nected.
Service Interval
Notify
(bit 10
set). The config-
ured battery
change interval
service has ex-
pired
No Battery
(bit 7
set) from UPS
software version
>= 2.0.0.6 and
firmware >=
25.1.I. The exis-
tence of the bat-
tery is checked
every minute.
UPS Fan Error
(bit 8 set) from
UPS software
version >=
2.0.0.7 and
firmware >=
40.1.I. The UPS
fan status is
checked each
minute.
Requires a
newer (second)
hardware revi-
sion!
Service Interval
Notify
(bit 10
set). The config-
ured battery
change interval
service has ex-
High
(bit 0 set) if
battery is fully
charged.
Charging
(bit 3
set)
No Battery
(bit 7
set) if no battery
was found.
No Battery
(bit 7
set). No communi-
cation to the bat-
tery (applicable
only for the model
with "Smart Bat-
tery" and not with
capacitors).
Over Temperature
(bit 9 set) was de-
tected and the
charging of the
battery was inter-
rupted.
Requires a newer
(second) hard-
ware revision.
Im-
plemented in the
UPS software ver-
sion >= 3.0.0.18.
Service Interval
Notify
(bit 10 set).
The configured
battery service in-
terval has expired.
None
None
Battery charge status
flags and special status in-
formation.