DCM-2 REPLACEMENT
The following procedure describes the steps
required to replace the Digital Control Module
(DCM-2) chassis assembly. These instructions
are applicable for DCM-2 Replacement kit
numbers 12-8061-75 & 12-8061-78 (for model
22-309) and 12-8061-85 & 12-8061-88 (for model
22-409).
The Group 22 operating parameter table
provides a list including some of the more important
parameters that may require configuration when
replacing a DCM-2. Review and obtain these
settings from the original DCM via HART or
serial port commands if possible, so they may
be configured on the new DCM-2. A DCM serial
cable kit is included with the DCM-2 replacement
kit.
TABLE 2 - GROUP 22 OPERATING PARAMETERS
(These values will be used to check the calibration of the actuator after the replacement DCM-2 is installed).
Operating
Parameters
Recorded
Value
HART Interface
HART
Menu
Variable
Name
Default
Value
Command
Default
Value
Drive Rotation (Increasing Signal)
5A
Drive Dir
CW
drvrotation
0 (CW)
Operation Mode
7
Op Mode
Follow
opmode
0 (follow)
Torque Zero
5E
Trq Null
0
*
torq0K
0
*
Torque Constant
5E
Trq Const
550
*
torqconst
550
*
CPS Volts at 0 Degrees
5B
CPS Zero
1.300
cpsvat0deg
1.000
CPS Volts per 100 Degrees
5B
CPS Span
2.400
cpsvper100deg
4.000
Travel
5A
Travel
100.00
travel
100.00
Demand LOS Threshold (mA)
5C
DemLimLwr
3.20
demlos
3.20
Demand LOS Mode
5C
LOS Mode
Stay
demlos
sip
Demand LOS Go To Position (%)
5C
LOS Pos
50.00
demlosgtp
50.00
0% Demand (mA)
5C
DemRngLwr
4.00
dem0pctma
4.00
100% Demand (mA)
5C
DemRngUpr
20.00
dem100pctma
20.00
Stall Time (Sec)
5
Stall Time
300
stalltime
300
Demand Function
5C
Dem Curve
Linear
demfunc
linear
Step Size
5
Step Size
0.10
stepsize
0.10
IO Mode
5D
Feedback
Enabled
iomode
1 (fdbk)
0% Feedback (mA)
5D
FB RngLwr
4.00
fdbk0pctma
4.00
100% Feedback (mA)
5D
FB RngUpr
20.00
fdbk100pctma
20.00
Torque Enable
5E
Trq/Thrust
Enabled
torqenable
1 (enabled)
Over Torque Stop
5E
Ovt Prot
Disabled
ovtstop
0 (disabled)
Polling Address
4
Poll Addr
0
polladr
0
Drive Model
4
Model
22-309
drvmodel
12 (22-309)
*Default values only – The specific numbers for these values are unique to each actuator and are determined during manufacture.
These specific numbers are noted on a tag affixed to the actuator body within the Electronics Compartment. Default values should
only be used if the specific numbers are unknown.