Page
42
Get
Current
Configuration
File
Display
Configuration
Error
Log
Enable
Rel
Ctl.
Firmware
Upgrade
Select 6),
to list any errors in uploading or
downloading the configuration file, the
unit will display either:
no errors
Press CR to continue
or
1. No communication with rpc at mod 3 port 1 (MRP:5)
Press CR to continue
Select 5),
to allow the admin to get a copy of
the current unit configuration file from the
unit and FTP’s it to a computer. The
configuration file to be uploaded is named
“confupload”. The file may be opened with
any ASCII or text file editor.
NOTE:
Save a copy of the “confupload” file under
a different name, just in case a mistake is made that
prevents the unit from operating properly. If the
unit appears to not respond, power-cycle the unit
and type semi-colon five times. If it appears the
unit is still not responding, follow the reset
procedures to reset the module.
Enabling this will allow the system configuration
file to be retrieved via ftp
Enable Configuration File Retrieval? (Y/N)
Select Get Current Configuration
File and the unit will display.
A YES response and the unit will
display the following:
/var/confupload file created and ready for ftp
retrieval
Waiting to send configuration file
-----------------------------------------------------
-----------------------------------
At this point FTP the file to your computer. A Successful
file retrieval and the unit displays:
get of configuration file complete
Unsuccessful file retrieval and the
unit displays:
***error in config upload file or transfer operation***
Select 7),
to upgrade the outlet controller firmware,
the unit will display the available controllers:
RPC Firmware Upgrade Menu
RPC10 (2 ,1).........1
Device B (2 ,2).........2
DS-RPC (3 ,1).........3
Enter Request :
Select the controller to be upgraded and the unit will
ask if this is the correct controller to enable firmware
upgrade. It will also tell you which port you are
connected which will determine which method to
upload the firmware.
If the unit displays the
following, type
“Y”
at
the prompt. The unit
will wait for the ASCII
file to be transfer. An
error will occur if the
terminal program
Upgrading RC firmware on RPC at module 2, port 1.
Enable update of Relay Controller firmware via Console (RS232) port.
Enabling will reset Ethernet Module when Configuration is exited
Enable Firmware Upgrade ? (Y/N) y
Send RC firmware file using ASCII file transfer option
on your Terminal program.
Waiting for RC firmware.
-------------------------------