Shutdown
code
Description
Probable causes
Checking / solution
5v[13
Communication error with
the SCU PCB
4
Bad connection with BUS
4
SCU PCB missing from
connection box
4
Check the wiring
4
Carry out automatic detection
5v[15
Gas pressure too low
4
Non-existent or insufficient
circulation
4
Incorrect gas switch Gps
adjustment (connected to
PCB SCU)
4
Check that the gas valve is fully opened
4
Check the supply pressure
4
Check whether the Gps gas pressure
control system has been correctly fitted
4
Replace the Gps gas pressure control
system if need be
5v[16
(1)
Configuration error
4
Internal fault in gas/air unit
4
Replace the gas/air unit
5v[17
(1)
Configuration fault or
default parameter table
incorrect
4
Parameter fault in gas/air unit
4
Replace the gas/air unit
5v[18
(1)
Configuration error (Boiler/
PSU not recognised)
4
Incorrect PSU for this boiler
4
Replace the PSU
5v[19
(1)
Configuration fault or
parameters
df
-
dV
unknown
4
Reset
df
and
dV
4
Reset
df
and
dV
5v[20
(1)
Configuration procedure
active
4
Active for a short time after
switching on the boiler
4
No action required (Normal behaviour)
5v[21
Communication fault
4
Internal fault in gas/air unit
4
Replace the gas/air unit
5v[22
No flame during operation
4
No ionization current
4
Purge the gas supply to remove air
4
Check that the gas valve is fully opened
4
Check the supply pressure
4
Check the operation and setting of the gas
valve unit
4
Check that the air inlet and flue gas
discharge flues are not blocked
4
Check that there is no recirculation of flue
gases
5v[25
Internal fault in gas/air unit
4
Replace the gas/air unit
(1) These lock-outs are not stored in the fault memory
9.2.2.
Lock out
If the blocking conditions still exist after several start up attempts, the
boiler will switch into locking mode (fault). The boiler can only start
operating again once the causes of the lock-out have been rectified
and after pressing the
J
key.
In the event of a fault, the status signal for the
B
button flashes
red. The meaning of the error codes is given in the error table:
Status signals
Description
Code
Error code
1
(1 times red signal) Sensor error
e[02
/
e[03
/
e[04
/
e[05
/
e[06
/
e[07
/
e[08
/
e[09
/
e[10
/
e[11
/
e[35
Error code
2
(2 times red signal) Overheat temperature protection
e[12
/
e[41
Error code
3
(3 times red signal) Ignition fault
e[14
/
e[16
/
e[36
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
9. Troubleshooting
02092014 - 7619497-02
65